Installation standards


Electrical theory Acronyms Installation standards Capacitors SupplySystems Automation Sensors Controllers and modules Control and Safety MicroProcessor PCboard References About us

Electrical theory
Acronyms
Installation standards
Capacitors
SupplySystems
Automation
Sensors
Controllers and modules
Control and Safety
MicroProcessor
PCboard
References
About us

 

-------------==============--------------

This section is very much a work in progress -

Read it conjunction post regarding installation

SANS    
Mains switch can be combined 3p circuit breaker

or

 3phase supplying single phase loads can be 3pole isolator and three single pole circuit breakers (prefferred)

   
Tee joints accessible & neutral must still be a continuous    
6.1.5 A maximum of three conductors may be connected to any one terminal provided that the terminal has the correct rating.    
     
     

-------------=============-------------

Conductor sizing

SANS    
Neutral same as phases unless 3rd harmonic and  imbalances    

Cable rating factors

Rated current size 6.2(a) to 6.9(a)
 

Correction factor for ambient temperature not 30DegC – Table 6.10
 

 

   

Calc a cable size


Buried factors:

Soil temperature Not 25DegC correction factors Table 6.11
 

IF UNDERGROUND: Soil thermal resistivity NOT 1.2K.m/W oil correction factors Table 6.12 -degrees Kelvin-meter per watt
This is interesting -its here but there is no way one can determine the correct values; I would have thought there is a chart somewhere to use around geopraphical areas...but there is noting. and the worst factor is 0.64...it will calculate to nearly double cable size.

Question: What to do if some cable in roof and half in ground?  I guess worst case applies. The regs does not say.

Popular methods of installation:

Method 2: House wiring - Single-core non
sheathed cables (wires) in metallic or no
metallic conduit on a wall or ceiling

Cables(wires) in conduit embedded in masonry, brickwork, concrete, plaster or
the like (other than thermally insulating materials)

Single-core cables in skirting or trunking

Method 3: Sheathed cables (FTE) embedded direct in masonry, brickwork, concrete, plaster or the like (other than thermally insulatingmaterials)

Sheathed cables clipped direct to or lying
on a non-metallic surface or bunched


Grouping factors:
Grouping and number of cables on racks or trays (see table 6.14);
 

Grouping and number of cables in a trench (see table 6.15);


Grouping and number of cables buried directly in the ground (see tables 6.11, 6.12, 6.13 and 6.16);


Neutral imbalance (see table 6.17);
 

Harmonics (see table 6.18); and
 

Direct solar radiation (see table 6.19).

 

   

---------===============-------------

     
SANS:

SANS 10142-1:2009

IEC  
Introduction
In this edition an attempt has been made to move towards the IEC codes:
extra low voltage (below 50 V) and d.c. applications (up to 1,5 kV) have been
introduced as new requirements owing to the extensive usage of, and
increased fire risk that result from, high load currents. This part of
SANS 10142 does not intend to cover the LV control circuits of machinery or
system components that are external circuits between separately installed
parts of the machinery or system components.
This part of SANS 10142 includes certain provisions which are for
information and guidance only. These provisions do not use the word "shall"
and they can be found in the text, in the notes and in the informative
annexes. Except in tables, notes are always for information only.
   
Short Circuit Protection: PSCC

6.7.3.2Unless other means of short-circuit protection are used, a short-circuit protective device shall be installed at any point where there is a change in the characteristics of a conductor (such as a change in nominal cross-sectional area).
NOTE Safe short-circuit protection of PVC insulated copper cables will normally
be ensured if the cross-sectional area of the conductor (in millimetres squared) is at least numerically equal to the prospective short-circuit current (in kiloamperes).
This is based on a maximum clearing time of less than one electrical cycle which is typical of LV short-circuit protective devices. Amdt 6

6.7.3.3 With particular reference to socket-outlets and luminaire supplies, the cross-sectional area of PVC insulated conductors shall comply with the calculated prospective short-circuit current requirements (see also the note to 6.7.3.2) for all points of consumption that fall within the limits of 6.7.3.4. Amdt 3

 
6.7.3.4For the purpose of protection against short-circuit current in PVC
insulated cables (of a
cross-sectional area <4 mm
2), the first 5 m in
single-phase circuits and 10 m in multiphase circuits are regarded as
being fault free. Amdt 3

   
Plug sockets

 

 

 
Lighting

 

   
RCD

6.7.5.2 Industrial type single-phase and three-phase socket-outlets (including "welding" socket-outlets) shall comply with the requirements of SANS 1239, and, except as allowed in 6.7.5.5 and 7.10.1.6, shall have earth
leakage protection if the circuit is intended to supply portable or stationary class I appliances.

   
     

-------------===========--------

Relationship between impulse withstand voltages of equipment and over voltage categories.

  4.5.3.2.2 IEC 60 364  
 

Different categories of overvoltage exist for equipment.

category IV = for use at, or in the proximity of, the origin of the installation, forexample, upstream of the main distribution board. Cat IV has a very high impulse withstand capability providing the required high degree of reliability.

NOTE: i) Examples of such equipment are electricity meters, primary overcurrent protection devices and ripple control units.

Category III - for fixed installation downstream of, and including the main distribution board, providing a high degree of availability.

NOTE: ii) Examples: DBs, circuit-breakers, wiring systems (see IEC 60050-826,
definition 826-15-01), including cables, bus-bars, junction boxes, switches, socket-outlets) in the fixed installation, and equipment for industrial use and some other equipment, e.g. stationary motors with permanent connection to the fixed installation.

Category II = for connection to the fixed electrical installation, providing a normal degree of availability normally required for current-using equipment.

NOTE: iii) Examples: Household appliances and similar loads.

Category I is only suitable for use in the fixed installation of buildings where protective means are applied outside the equipment –to limit transient overvoltages to the specified level.

NOTE: iv) Examples of such equipment are those containing electronic circuits like computers, appliances with electronic programmes, etc.
Category I equipment shall not have direct connection to a public supply system
 
  4.5.3.3.2.1 External hi voltage influences: Where an installation is supplied by, or includes, an overhead line, and the keraunic level of the location is greater than 25 days per year (AQ 2), protection against overvoltages of atmospheric
origin is required. The protection level of the protective device shall not be higher than the level of
overvoltage category II, given in Table 44B.
 

-----------=============---------

Earthing

  IEC  
  Machine safety: Ref: Panel design Rittal

Excerpt from VDE 0113-1/DIN EN 60 204-1 and  IEC 364-5-54, 543.1 or EN 60 439-1, 7.4.1.7, depending on
which applies.

Machine safety;
Electrical equipment of machines, general requirements 5.2 External PE conductor connection

One terminal for connecting the external PE conductor must be provided in the vicinity of the corresponding external conductor contact.
 

The terminal must be  dimensioned such that it facilitates the connection of
an external copper conductor with a cross-section in accordance with the following table.
If a PE conductor from a material other than copper is used, the terminal size must be selected accordingly

Minimum cross-section of copper external PE conductor

also internal PE condiuctor most cases meet requirement if the same as external

8.2.3 Continuity of the PE conductor system
All exposed conductive parts in the electrical equipment and the machine(s)
must be connected to the PE conductor system.
Unless no electrical mounted (or PELV used) lids, doors or cover plates must also be connected (cannot depend on higes, screws) ,
If a part is removed for some reason (e.g. regular servicing), the PE conductor system for the remaining parts must not be interrupted.

8.2.5 Parts which need not be connected to the PE conductor
It is not necessary to connect exposed conductive parts to the PE conduc
tor system if these are mounted in such a way that they do not pose any risk
because:
– they cannot be contacted over a large area or surrounded by a
person’s hand and have small dimensions (less than approximately
50 mm x 50 mm)
or
– they are arranged in such a way that contact with active parts or an
insulation fault is unlikely.
This applies to small parts such as screws, rivets and identification labels,
and to parts within enclosures, irrespective of their size (such as electro
magnets of contactors or relays, and mechanical parts of devices).

Labelling:

ONLY the terminal for the external PE conductor labelled: “PE”.

Other terminals for PE labelled with the EARTH symbol 417 IEC 5019 and 15.2.2.or by using the two-colour combination GREEN/YELLOW.

8.2.7 PE conductor connection points
All PE conductors must be connected in compliance with 15.1.1.
PE conductors must not be connected to connection parts used to secure or
connect devices or parts.
Each PE conductor connection point must be labelled as such using the
symbol 417-IEC-5019. Optionally, terminals for the connection of PE con
ductors may be indicated as such via the two-colour combination GREEN/
YELLOW.

Table 1

Minimum cross-section of copper external PE conductor
Cross-section S
of external conductors
for mains connection
(mm2)



 
Minimum cross-section
of external PE conductor
(mm2)
S ≤ 16  S
16< S ≤35 16
S > 35  S/2
   

 

------------------===============------

Enclosures:

For operator control requirement "controlsafety".

  IEC EN 60 529.  
  13.4 Enclosures, doors and openings
Locks used to secure doors and covers should be captive.
Windows intended for monitoring the display devices inside must be made from a material
that is capable of withstanding mechanical stresses and chemical influences, e.g. toughened glass, polycarbonate plates (3 mm thick).
We advise that enclosure doors should have vertical hinges, preferably of a type where the doors can be lifted out.
The opening angle should be at least 95°.
The doors should be no wider than 0.9 m.
 
  13.3 Minimum Protection categories
Enclosures of switchgear must have a minimum protection category of IP 54 (see EN 60 529).
Unless IP22 for Vented enclosures which only contain motor starter resistors, dynamic braking resistors or similar equipment:
– IP23 for Motors
–IP 33 - Vented enclosures containing other equipment:.
 
  Ref: Panel design Rittal

6.3. By using PELV in accordance with 6.4, protection against both direct contact and indirect contact is ensured.

6.2.3, must be applied to each circuit or each part of the electrical equipment.

6.2.1 Protection via enclosures (housings) Active parts must be positioned within enclosures which meet the relevant requirements from sections 4, 13 and 16.

For top covers of enclosures that are readily accessible, protection agains direct contact, protection category IP 4X or IP XXD, must be met as a minimum requirement (see EN 60 529).

It must only be possible to open an enclosure (i.e. opening doors, removing lids, covers and the like) if one of the following conditions is met:

a) Use of a key or tool for access by electricians or electrical staff if switching off the equipment is inappropriate. The master switch may be switched with the door open, if necessary.

b) Disconnection of active parts within the enclosure before the enclosure can be opened.

Door interlocking handle. Overide by special tool is allowed

and

– when the door is closed, the lock is automatically reactivated.

This is applicable to all entrances to the enclodure

---------=====-----

All parts which remain live after disconnection must provide protection

against direct contact, protection category IP 2X or IP XXB (see EN 60 529),

as a minimum requirement.

Such parts must be labelled with a warning notice in accordance with 18.2.

The mains connection terminals of the master switch are exempted from this

ruling, provided the latter is housed in a separate enclosure.

c) Opening without using a key or tool and without deactivating the active parts must only be possible if all active parts are protected against direct contact in accordance with protection category IP 2X or IP XXB (see EN 60 529) as a minimum requirement. If covers provide this protection, they must either only be removed using a tool, or else they must automatically deactivate all protected active parts when the cover is removed.

 

 

 

-------------===========--------

 

Wireways:

IEC  

Ref: Panel design Rittal

 
   

---------------==============---------------

Found this table from Panel design Rittal -

Further discussed under circuit breakers

---------------=============-------------

IP rating of panel see "Standards"

---------================--------

Enclosure mechanical protection: IK code

Ref: Panel design Rittal

Protection category to DIN EN 50 102, protection from external mechanical loads (IK code)

After testing, the test piece must be fully functional.

In particular, the protection category to EN 60 529 must not be impaired (e.g. hinge bent, seal cut, gap in friction-locked connections or similar).
Safety and reliability must not be impaired.

----------------============----------------

Cables:

-----------------==============-----------

Cable ratings:

--------------==================-------------

Busbar ratings Table 1

---------------==============-------------

Current correction for Cu busbar systems. Because of HOW we normally use barsbar systems (in a panel etc)...we can use them at higher ratings.  
 

In DIN 43 671 on measuring continuous current for copper busbars, Table 1
shows continuous currents which generate a busbar temperature of 65°C in
busbars of E-Cu with a square cross-section in internal installations at an air
temperature of 35°C.

For other temperature conditions, Figure 2 of DIN 43 671 shows a correction
factor which is multiplied by the original rated current to obtain the new permissible rated current.

How to:

Bar cross-section 30 x 10 mm
Permissible bar temperature 85°C
Ambient temperature 35°C
From Figure 2 correction factor K2= 1.29
I1= IN * k2= 573 A * 1.29 = 740 A
To this end, 8 % = 60 A is added to the (assumed) more favourable emission
level of the bars, producing the new permissible rated current:
IN= I1+ I1 8/100 = 740 A + 60 A = 800 A

-----------======================-----------

Busbar resistance table

----------================---------------

Re panel design and responsibilities:

Type testing:

Type tested: (TTA)The final product is un- modified from the manufacturer -as was tested.

Partial Type tested (PTTA) e.g. A panel mnf by first party is completed by a second party who has to also certify compliance.

"Type testing" in another context also imply that not every product is tested eg a compliance testing facility. Only a sample was tested and so compliance has to ensured by a different system eg ISO mnf procedures.

Panel design re standards:

    UL
    Important notes for the use of busbar systems to UL 508
One of the principal changes in UL 508A is the amendment to the required
creepage distances and clearances for feeder circuits.

The following distances are required for applications > 250 V:
Between phases:
● Creepage distance 50.8 mm (2 inches)
● Clearance 25.4 mm (1 inch)
Between phase and earthed, uninsulated metal parts:
● Creepage distance 25.4 mm (1 inch)
● Clearance 25.4 mm (1 inch)


Rittal RiLine60 complies with these requirements.

However, users should bear in mind a small number
of differences from the IEC version:
● Special UL busbar supports for flat bars and Rittal PLS with increased
creepage distances and clearances.
● Use of the Rittal RiLine60 base tray is required in order to comply with
the necessary minimum distances from the mounting plate.
58

------------===============-------

1. Rated currents
For untested busbar applications, UL 508A specifies a current carrying capacity of 1000A/inch2 (1.55 A/mm2) in the absence of testing.
This value may be higher if the product or application has undergone suitable testing. Rittal has conducted extensive testing in this respect in order to give users the maximum benefits when using the RiLine60 busbar system. The benefit of such testing is that busbar systems with higher rated currents may be used than permitted by the default value. For example, a busbar with the dimensions 30 x 10 mm can carry 700 A instead of 465 A.

-=-----------------==============--------

2. Terminals for factory or field wiring
Terminal approved for factory wiring, it may only be used in switchgear assembly by suitably trained professionals.
Approved for field wiring can only be used in the field (e.g. on a construction site)
the component must be approved for field wiring.

-----------=============--------

 

------------=================-----------------

Panel SCCR - Short circuit Current Rating

  NEC/UL
 

Since 2006, all UL Listed industrial control panels are

now marked and labeled with a Short Circuit Current Rating

How to determine SCCR:

1: Test the panel at its labeled SCCR in a witnessed test by a National Recognized Testing Lab (NRTL).

OR

2:  Apply the standardized tables of UL 508 A, standard for

industrial control panels.

Note: A panel SCCR can be increased by using current limiting devices. Ref Littelfuse SCCR whitepaper.

 

---------------===============-------------

 

-------------===============--------------

Mixed loads: looks like they could not decide what IS a mixed load.

SANS    

Intro notes:

6.16.1.1 Fixed appliances is not part of  electrical installation

When a fan is part of a luminaire it becomes an appliance.

----- 

6.16.1.4 Where a fan or heater is included in a luminaire, the luminaire is
regarded as a fixed appliance. If the luminaire circuit is protected by earth
leakage, a disconnector is not required (see 6.9.3.1).Amdt 1 -

--------

6.16.1.3The power supply to every fixed appliance, except luminaires,
shall be supplied through


a) a disconnecting device that disconnects both live conductors in a
single-phase supply and all phase conductors in a multiphase supply,

or Amdt 3


b) a socket-outlet Amdt 3
that is directly accessible at all times that any person is exposed to such
appliance while the supply is on.

In the case of a remotely installed
appliance, the position of the disconnecting device shall be indicated by means of a notice in close proximity to or on the appliance. Amdt 3

 

 

 

 

6.15.4 Mixed loading of circuits NOT ALLOWED

Mixed loads not allowed but you can mix sockets, luminaires and fixed appliances. Really?

except as allowed in 6.15.4.2 and 6.15.4.3, there shall be no mixed loading of circuits.

(See also 6.16.3.2.3.) Amdt 5
6.15.4.2

A single-phase circuit that has overcurrent protection rated at not more than 20 A may supply a mixed load of

a) socket-outlets rated at not more than 16 A and fixed luminaires,

b) socket-outlets and fixed appliances, or
 

c) socket-outlets, luminaires and fixed appliances.

Why this strange list of A,B,C


NOTE The number of points need not be limited. I don't think so, especially not mixed loads!

My take:

a) CB<=20Amp (domestic)

b and c) circuits bigger then 16Amp sockets and has to comply with  6.7.5. and

NOTE 1 See 7.1 for the conditions under which a socket-outlet may be installed in a bathroom.
NOTE 2 See 6.16.1.6 for the conditions under which a socket-outlet may be used for the connection of fixed appliances. 

 

Plug rating>=16Amp and fixed luminaires

EL Protection

 

 

   

-------------=============--------------

STANDARDS and references:

Why is the plug socket rating 16Amp and not 20Amp?

Why for a plug(feeder) circuit the circuit breaker is 20Amp rated, the wire size is normally 2.5mm, but the sockets in that circuit are 16Amps! What's up with that?

SANS      
6.15.3 Single-phase circuits that only supply socket-outlets rated at 16A

Single-phase circuits that only supply socket-outlets rated at not more than 16 A,
a) shall have overcurrent protection;
b) shall use conductors that are rated at not less than 16 A;

c) shall, if the circuit protection is rated at more than 20 A, use only protected socket-outlets, with, as far as is practicable, discrimination between the protective devices for the circuit and the protective devices associated with the socket-outlets.

The protective device of a protected socket-outlet shall
1) have a fixed rated current that does not exceed the rating of the socket-outlet,
2) be mounted next to the socket-outlet that it protects,
3) provide protection against overload currents,
4) provide protection against short-circuit currents, unless short-circuit protection is provided by a separate device, for example on the distribution board,
5) if it needs the protection of a back-up short-circuit device, be
marked with the required or maximum rating of the back-up
device,
6) if it protects more than one socket-outlet, be so installed that all the socket-outlets are connected in parallel, have the same rated current, and are mounted next to the device, and
7) if it is a circuit-breaker, comply with the requirements of 6.8.2.


NOTE In the interest of safety, the use of the building, the convenience of the occupants and the possibility of heating and cooling equipment being connected to socket-outlets, should be considered when the number and position of points of
consumption are being determined.

 

     

---------================----------

Test: Max volt drop - This has never been a test - its a calculation.

SANS    

5.2.2 Voltage drop
5.2.2.1When all conductors of an a.c. installation are carrying their
maximum estimated load, the difference in voltage (the voltage drop)
between the point of supply and any point of outlet or terminals of fixed
appliances shall not exceed 5 % of the standard voltage or of the
declared phase-to-neutral voltage (see also 6.2.7)
.

In the case where
reticulation is part of the electrical installation after the point of supply, the
5 % voltage drop shall be calculated to include the reticulation part of the
installation (for example, in the case of a housing scheme where further submetering with a further point of control is installed for individual consumers).

Means: The maximum volt drop from the supply point to the furtherst end of an installation shall be max 5% of Vsupply.

Same for DC

   
     

 

SEE HERE FOR THE COMPLETE POST / TOPIC LIST.

 

References: Thank you to the following who unwittingly or wittingly collaborated to build knowledge. For any infringements, apologies. Let us know here:

Copyright issues