ElectroStores
Home SupplySystems Switches Relays Circuitbreakers Automation Metering Sensors Controllers and modules Standards Acronyms and definitions Training Control and Safety About us

 

Up
Fuses

Circuit breakers

Definition:

Circuit breaker:- A manually (or remote) operated device capable of making, current-carrying and breaking currents under normal circuit conditions and also automatically breaks a circuit under specified abnormal conditions such as overload and short circuit currents 

Definition:

Circuit breaker:- A mechanical switching device capable of protecting the circuit wiring, capable of making, carrying and breaking currents under normal circuit conditions and also making, carrying for a specified time and breaking currents under specified abnormal circuit conditions such as those of short circuit (IEC 947-1).

 

 

Acronyms:

SCPD Short-Circuit Protective Device
CB  
MCB Miniature circuit breaker - 0.5 o 125Amp,
MCCB A circuit breaker having a supporting housing of moulded insulating material forming an
integral part of the circuit breaker (IEC 947-2).
ACB Air circuit breaker

 

 
In depth look at the tripping curve:

---------===========---------

Description: Ground-fault Characteristic Curve

Figure 4 – Ground-fault Characteristic Curve

 

-----------==========--------

 

Definitions and explanations:

In= Nominal trip current indicated on CB.

 

 

 

Interrupting short-circuit current:-
As an example, let us consider a quick acting, current limiting circuit breaker a described previously.
To limit the short-circuit current already at its initiation, the main contacts must be opened by the striker within a few milliseconds. A very fast acting device
may need less than 1ms for this. An arc is struck immediately, which driven towards the arc chamber, delivers a high arc voltage. As a simplification, the ar
voltage can be considered as an equivalent additional resistance connected in series to the current circuit which immediately limits the rising short-circuit
current.

Let-through energy (Joule integral) of the fast acting circuit breaker 140M
The energy of the short-circuit current integrated over a time period, also called
the let-through energy I2t (Joule integral), indicates how the components installed downstream of the circuit breaker, especially switching devices like a contactor, are less stressed when protected by a current limiting circuit breaker instead of a current-zero interrupting type.
 

Note : Although popularly called the let-through energy, the Joule-Integral gives
only an indication of the let-through energy and do not have the dimension of
energy. The Joule-Integral multiplied the resistance of the current path is actu
ally the let-through energy.
 

The resulting low let-through values of the current limiting circuit breaker cause
no or very little damage to the components or devices installed downstream of
the circuit breaker. With the right choice of the various components, strongly
welded contacts of contactors or severe damage to the connecting wiring or bus
bars due to uncontrolled arcing can be prevented.

---------------=============-------------

Motor protection circuit breakers:-

Adjustable, current dependant time-delayed overcurrent release protects against thermal overloading.

The ambient air temperature compensation and a precise calibration of the overcurrent release mechanism assures an exact and reliable tripping. Often a differential release for the protection against the loss of a phase is integrated in the device.

After the interruption of a short-circuit, the tripping characteristic must not alter without any outwardly visible indication.

Fig. 1.4-3: Tripping curve of a circuit breaker with motor protective characteristics.

The grey line indicates the current form of a normal motor. After the rated speed is reached (here after about 1.5s), the starting current (6 x In) reduces to the rated current of the motor(1xIn).
a) Time-current characteristic of the bimetallic release
b) Time-current characteristic of the magnetic release
c) Characteristic of the motor

 

 

 

Current limiting circuit breaker

Interrupting short-circuit current:-
As an example, let us consider a quick acting, current limiting circuit breaker a
described previously.
To limit the short-circuit current already at its initiation, the main contacts must
be opened by the striker within a few milliseconds. A very fast acting device
may need less than 1ms for this. An arc is struck immediately, which driven
towards the arc chamber, delivers a high arc voltage. As a simplification, the arc
voltage can be considered as an equivalent additional resistance connected in
series to the current circuit which immediately limits the rising short-circuit
current.

Let-through energy (Joule integral) of the fast acting circuit breaker 140M
The energy of the short-circuit current integrated over a time period, also called the let-through energy I2t (Joule integral), indicates how the components installed downstream of the circuit breaker, especially switching devices like a contactor, are less stressed when protected by a current limiting circuit breaker instead of a current-zero interrupting type.
 

Note : Although popularly called the let-through energy, the Joule-Integral gives
only an indication of the let-through energy and do not have the dimension of
energy. The Joule-Integral multiplied the resistance of the current path is actually the let-through energy.
 

The resulting low let-through values of the current limiting circuit breaker cause
no or very little damage to the components or devices installed downstream of
the circuit breaker. With the right choice of the various components, strongly
welded contacts of contactors or severe damage to the connecting wiring or bus
bars due to uncontrolled arcing can be prevented.

 

Other special characteristics circuit breakers:

  1. Current-zero interrupting type:-
  2. Current limiting type:-Interrupt the current during the initiation of the short-circuit, before the full prospective value can be attained.
 
1.2.2.2. Current-zero interrupting type of circuit breaker (“Basics of Circuit breakers  -
thanks to : http://electrical-engineering-portal.com/download-center/electrical-software/selection-of-mccb-elcb-for-main-branch-circuit
 
 
1.2.2.3. Special features of the current limiting circuit breaker
In order to reduce the mechanical (due to electro-dynamic forces) and thermal
stresses on the object to be protected, the current must be interrupted right during
the initiation of the short-circuit, before the full prospective value can be attained
(as for example to avoid the welding of the contactor contacts).
This is achieved by :
• Quick opening of the main contacts.
• Rapid build-up of a high arc-voltage (move the arc quickly away from the
contact tips and guide it to the arc chamber).
 
The effects of the reduced let-through values are :
• Reduction of the electro-dynamic forces on the bus-bars (as for example
increased spacing between supports).
 
• Reduction of thermal stresses. The welding of the contacts of contactors can
be prevented. Over-dimensioning of the contactors can be avoided or at least
kept within reasons. The result is reflected in the short-circuit co-ordination
tables - compact starter combinations with components selected mostly on
the basis of their rated currents.
The current limiting circuit breakers are used in a wide field of applications. It is
no longer necessary to carry out complex calculations of the short-circuit current
at each point of the network where a circuit breaker is installed. The subject of
short-circuit co-ordination takes about as much planning effort as in the case of
fuses.
The circuit breaker should be constructed in such a way that it can interrupt the
short-circuit current under all possible situations without any problem whatsoever.
The features, which make the planning with circuit breakers as simple as that
with fuses, are :
• High breaking capacity makes calculation of short-circuit current superflu-
ous: in actual applications, the fault level (prospective short-circuit current)
at the point where circuit breakers for motor branch circuits are installed lie
mostly in the range of 1…20kA. If the breaking capacity of the circuit 
breaker is higher than this, no further calculation is necessary. The circuit
breakers can be utilised in any point of the installation without calculations
for its dimensioning, similar to a high rupturing capacity fuse.
• Low let-through values: the contactors connected downstream are less
stressed as the short circuit current is appreciably limited by the circuit
breakers. Short-circuit co-ordination is simplified and it is not necessary to
consult the short-circuit co-ordination tables (the manufacturers perform
 
tests for the short-circuit co-ordination and supply tables in accordance with
the IEC 947-4-1 for, as for example, types "1" or "2"). The combination of a
circuit breaker and a contactor, both selected on the basis of their rated cur-
rents, can in most of the cases fulfil the requirements of the type of co-ordi-
nation "2", without any other considerations.

 

1.2.2.2. Current-zero interrupting type of circuit breaker (“Basics of Circuit breakers -

thanks to : http://electrical-engineering-portal.com/download-center/electrical-software/selection-of-mccb-elcb-for-main-branch-circuit

1.2.2.3. Special features of the current limiting circuit breaker

In order to reduce the mechanical (due to electro-dynamic forces) and thermal

stresses on the object to be protected, the current must be interrupted right during

the initiation of the short-circuit, before the full prospective value can be attained

(as for example to avoid the welding of the contactor contacts).

This is achieved by :

Quick opening of the main contacts.

Rapid build-up of a high arc-voltage (move the arc quickly away from the

contact tips and guide it to the arc chamber).

The effects of the reduced let-through values are :

Reduction of the electro-dynamic forces on the bus-bars (as for example

increased spacing between supports).

Reduction of thermal stresses. The welding of the contacts of contactors can

be prevented. Over-dimensioning of the contactors can be avoided or at least

kept within reasons. The result is reflected in the short-circuit co-ordination

tables - compact starter combinations with components selected mostly on

the basis of their rated currents.

The current limiting circuit breakers are used in a wide field of applications. It is

no longer necessary to carry out complex calculations of the short-circuit current

at each point of the network where a circuit breaker is installed. The subject of

short-circuit co-ordination takes about as much planning effort as in the case of

fuses.

The circuit breaker should be constructed in such a way that it can interrupt the

short-circuit current under all possible situations without any problem whatsoever.

The features, which make the planning with circuit breakers as simple as that

with fuses, are :

High breaking capacity makes calculation of short-circuit current superflu-

ous: in actual applications, the fault level (prospective short-circuit current)

at the point where circuit breakers for motor branch circuits are installed lie

mostly in the range of 1…20kA. If the breaking capacity of the circuit

breaker is higher than this, no further calculation is necessary. The circuit

breakers can be utilised in any point of the installation without calculations

for its dimensioning, similar to a high rupturing capacity fuse.

Low let-through values: the contactors connected downstream are less

stressed as the short circuit current is appreciably limited by the circuit

breakers. Short-circuit co-ordination is simplified and it is not necessary to

consult the short-circuit co-ordination tables (the manufacturers perform


 

tests for the short-circuit co-ordination and supply tables in accordance with

the IEC 947-4-1 for, as for example, types "1" or "2"). The combination of a

circuit breaker and a contactor, both selected on the basis of their rated cur-

rents, can in most of the cases fulfil the requirements of the type of co-ordi-

nation "2", without any other considerations.

-----------===========-----------


 

 

 

Types:

Thermal and or magnetic:

Hydraulic magnetic:

 

   
 

Tripping curves:

         
B        
C        
D        
E        
F        
         
1        
2        
2,3(LL)        
4        

Other special characteristics circuit breakers:

  1. Current-zero interrupting type:-
  2. Current limiting type:-Interrupt the current during the initiation of the short-circuit, before the full prospective value can be attained.
 

Summary: circuit breaker as load break switch

Analysis of a short circuit:-

The short-circuit current reaches its peak value after a quarter of the sinusoidal period, which is 5 milliseconds for 50Hz supply (4.2ms in the case of 60Hz as in the USA), assuming that the current is symmetrical, i.e. initiated at a current zero. This is to be prevented.

 

 

 

 

 
 

How shall a circuit breaker be rated:

SANS.5.2 NEC SANS    
         

 

An interesting note I found in NEC article 100 definitions:  was that the automatic means does not have to be an integral part of the circuit breaker - that is a surprise.gs For a circuit breaker it must, at a specific voltage (considering the circuit power factor) and the fault current equalling its rated breaking capacity or lower be capable of breaking the circuit. gs

Strange we don't find the "make" anywhere? gs

 

5.1.3 - EFP

5.2.5 - protection equipment

7.13 hiV apparatus

2.2.1 South African standards

SANS 152 (SABS 152), Low-voltage air-break switches, air-break disconnectors, air-break switch-disconnectors

 

SANS 156 (SABS 156), Moulded-case circuit-breakers.

SANS 556-1, Low-voltage switchgear – Part 1: Circuit-breakers.

SANS 767-1 (SABS 767-1), Earth leakage protection units – Part 1: Fixed earth leakage protection circuit-breakers.

SANS 61008-1/IEC 61008-1, Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs) – Part 1: General rules.

UL 508, Industrial control equipment. check his out in SANS 3.71 short-circuit protective device

SCPD device intended to protect a circuit or p

A

 
   

 

How is it selected for overload current protection
SANS10142: 6.7.x IEC 60364

 

NEC Article 230.42

6.7 Protection
6.7.1 Overcurrent protection
NOTE The term over current protection includes both overload protection (see 6.7.2) and short-circuit protection (see 6.7.3).

6.7.1.1
Each protective device shall have a rated current that does not exceed the lowest of the current-carrying capacities of any of the conductors of the circuit and shall have a minimum short-circuit rating of 2,5 kA.
 

6.7.2 Overload protection

6.7.2.1 Overload protection:
The rated current of the overload protective device shall not
exceed the current-carrying capacity of the conductor it protects, except in the case of circuits in which the presence of overload protection could create a dangerous situation, such as in circuits for lifting magnets

BTW: No mention of the component current ratings?gs

 

 



 

4.4.4.1

Reference:- ABB Comparison of tripping characteristics
for miniature circuit-breakers

For protection against overload, the protective device must be selected  based on the current carrying capacity

Ib In  Iz (standard)

Idesign Icb  Icable (mine)

and

I2 1.45 x Iz (standard)

Ioperation 1.45 x Icable (mine)

Ib= Design current of a circuit

In= Rated current of the protective device

Iz= Current carrying capacity of the cable in accordance with IEC/HD 60364-5-52

I2 = Current ensuring effective operation in the conventional time of the protective device

IEC 60364-4-43h

 


Where a feeder supplies continuous loads or any combination of continuous and noncontinuous loads, the rating of the
overcurrent device shall not be less than the noncontinuous load plus 125% of the continuous load.

Exception: Where the assembly including the overcurrent devices protecting the feeder(s) are
listed for operation at 100% of their rating, neither the ampere rating of the overcurrent device nor the ampacity of the feeder conductors shall be less than the sum of the continuous load plus the noncontinuous load.

Only breakers listed for 100% application,
and so labelled can be applied under the exception (for example loads Frame and R Frame 140G’s that are specifically marked and rated 100%).

Breakers without a 100% application listing and label are applied at 80% of rating
 

I could not find this in the NEC 2011

this is in 2011:

II. Branch-Circuit Ratings
210.19 Conductors — Minimum Ampacity and Size.
(A) Branch Circuits Not More Than 600 Volts.
(1) General. Branch-circuit conductors shall have an ampacity not less than the maximum load to be served. Where a branch circuit supplies continuous loads or any combination of continuous and noncontinuous loads, the minimum branch-circuit conductor size, before the application of any adjustment or correction factors, shall have an allowable ampacity not less than the noncontinuous load plus 125 percent of the continuous load.


Exception: If the assembly, including the overcurrent devices protecting the branch circuit(s), is listed for operation at 100 percent of its rating, the allowable ampacity of the branch circuit conductors shall be permitted to be not less than the sum of the continuous load plus the noncontinuous load.
 

Informational Note No. 1: See 310.15 for ampacity ratings
of conductors.
Informational Note No. 2: See Part II of Article 430 for
minimum rating of motor branch-circuit conductors.
Informational Note No. 3: See 310.15(A)(3) for temperature limitation of conductors.

b) Opening under overload conditions

1) Instantaneous or definite time-delay operation

The release shall cause tripping of the circuit-breaker with an accuracy of i10 O/. of the tripping current value of the current setting for all values of current setting of the overload

release.

2) Inverse time-delay operation. Conventional values for inverse time-delay operation are given in table 6.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IEC 60947-2:

7.2.5 Ability to make and break under short-circuit conditions

Subclause 7.2.5 of Part 1 applies with the following amplifications:

The rated short-circuit making capacity shall be in accordance with 4.3.5.1(Rated short circuit making capacity) and 4.3.5.3 (Standard relationship between short-circuit making and breaking capacities and related power factor, for a.c. circuit-breakers)

The rated short-circuit breaking capacity shall be in accordance with 4.3.5.2

The rated short-time withstand current shall be in accordance with 4.3.5.4

NOTE It is the manufacturer’s responsibility to ensure that the tripping characteristic of the circuit-breaker IS compatible with the capability of the circuit-breaker to withstand the inherent thermal and electrodynamlc stresses

---============-----

and the association shall comply with the requirements of 7.2.1.2.4, item a)

-----===========----

7.2.1 .2.4 Opening by over-current releases a)

b)

Opening under short-circuit conditions

The short-circuit release shall cause tripping of the circuit-breaker with an accuracy of

20% of the tripping current value of the current setting for all values of the current setting

of the short-circuit current release.

Where necessary for over-current co-ordination (see 2.17), the manufacturer shall provide Information (usually curves) showing. maximum cut-off (let-through) peak current (see 2.5 19 of Part 1) as a function of prospective current (r, m.s. symmetrical);

— /2t characteristics (see 2.18) for circuit-breakers of utilization category A and, if applicable, B for circuit-breakers with instantaneous override (see note to 8.3.5).

Conformity with this information may be checked during the relevant type tests in test sequences II and Ill (see 8.3.4 and 8.3.5).

NOTE It may be possible to provide other forms of data to verify co-ordination characteristics of circuitbreakers, for example, tests on combinations of short-circuit protective devices.

Opening under overload conditions

1) Instantaneous or definite time-delay operation

The release shall cause tripping of the circuit-breaker with an accuracy of i10 O/. of the

tripping current value of the current setting for all values of current setting of the overload release.

2) Inverse time-delay operation Conventional values for inverse time-delay operation are given in table 6.

At the reference temperature (see 4.7.3) and at 1,05 times the current setting (see 2.4.37

of Part 1), i.e. with the conventional non-tripping current (see 2.5.30 of Part 1), the opening

release being energized on all phase poles, tripping shall not occur in less than the

conventional time (see 2.5.30 of Part 1) from the cold state, i.e. with the circuit-breaker at the reference temperature.

Moreover, when at the end of the conventional time the value of current is immediately raised to 1,30 times the current setting, i.e. with the conventional tripping current (see 2.5.31 of Part 1), tripping shall then occur in less than the conventional time later.

NOTE The reference temperature is the ambient air temperature on which the time-current characteristic of the circuit-breaker is based. 4.7.3

Table 6 simply says

for lower/equal to 63Amps - at 1.05In circuit must trip after 1 hr only, if then raised to 1.3In it must trip ONLY within 1hr

at bigger then 63amps it becomes 2hr

They talk about this time as conventional time.

 

 
 

DEFINING THE TRIPPING CURVE

4.7.4 Tripping time setting of over-current releases


1) Definite time-delay over-current releases
The time-delay of such releases is independent of the over-current.

 The tripping time setting shall be stated as the duration in seconds of the opening time of the circuit-breaker, if the time-delay is not adjustable, or the extreme values of the opening time~ if the time delay is adjustable.


2) Inverse time-delay over-current releases
The time-delay of such releases is dependent on the over-current.

The time/current characteristics shall be given in the form of curves supplied by the
manufacturer.

These shall indicate how the opening time, starting from the cold state, varies with current within the range of operation of the release.

The manufacturer shall indicate, by suitable means, the tolerances applicable to these curves.
These curves shall be given for each extreme value of the current setting and, if the time
setting for a given current setting is adjustable, it is recommended that they be given in
addition for each extreme value of the time setting.
 

NOTE It is recommended that the current be plotted as abscissa and the time as ordinate, using logarithmic scales.

Furthermore, in order to facilitate the study of co-ordination of different types of over-current protection,

!t is recommended that the current be plotted as multiples of the setting current and the time in seconds on the standard graph sheets detailed in 5.6.1 of IEC 60269-1 and in figures 4(l), 3(11) and 4(11) of IEC 60269-2-1.

 
  Circuit breaker Reference temperature:

 lS/lEC 60947-2:2003

Unless otherwise specified – the operating value of overload releases other than those of the thermal type is independent of the ambient air temperature within the limits of -5 “C to +40 ‘C;

for releases of the thermal type, the values stated are for a reference temperature of +30 “C i 2 “C. The manufacturer shall be prepared to state the influence of variations in the ambient air temperature (see 7.2.1.2.4, item b)).

 

 

 
     

And short circuit currents:

SANS10142: 6.7.3    
 Short-circuit protection
6.7.3.1 At its point of installation, a short-circuit protective device shall be capable of breaking any over current up to the value of the prospective short-circuit current. (See also 6.7.4 on cascaded systems.)
   
 

And the impedance?

BS EN 60947-2 - calculating Zs    
In this case Zs is determined from the basic equation:- Zs Ia≤ UoCmin– which transposes to: - Zs≤ ((UoCmin)/Ia) where:-
 

Uo is the nominal voltage to earth.
Ia is the current required to achieve the disconnection time as given in the Regulations.
 

Cmin is the minimum voltage factor to take account of voltage variations depending on time and place, changing of transformer taps and other considerations.
 

NOTE: For a low voltage supply given in accordance with the Electricity Safety, Quality and Continuity. Regulations 2002 as amended, Cmin is given the value 0.95.

 

 

   
 
         

What does the standards say about Prospective fault current?

SANS 10142 IEC  
6.6.1.15 Switchgear shall be fully rated for withstanding the prospective
short-circuit current that could occur at that point in the system, unless
series-connected
(cascaded) systems are applied in accordance with
6.7.4.

6.6.1.16 Where the prospective fault level of the supply cannot be determined, a fault current meter may be used (see 8.5.2).
 

6.6.1.17 All disconnecting devices in a distribution board
a) shall be protected by a fully rated short-circuit protective device, and
b) when used in combination with a short-circuit protective device (see
6.7.4), shall have a conditional short-circuit current rating (see 3.22.1)
appropriate to its condition of installation, but of not less than 2,5 kA

 

   
       
         
         
 

 

  IEC 60947.2: 4.4: Utilisation categories  
  Table 4- Utilization categories
Category A

Circuit-breakers not specifically intended for selectivity under short-circuit conditions with respect to other short-circuit protective devices in series on the load side, i.e. without an intentional short-time delay provided for selectivity under short-circuit conditions, and therefore without a short-time withstand current rating according to 4.3.5.4.

Category B

Circuit-breakers specifically intended for selectivity under short-circuit conditions with respect to other short-circuit protective devices in series on the load side, i.e. with an intentional short-time delay (which may be B adjustable), provided for selectivity under short-circuit conditions. Such circuit-breakers have a short-time withstand current rating according to 4.3.5.4.

NOTE Selectivity is not necessarily ensured up to the ultimate shortcircuit breaking capacity of the circuit-breakers (for example in the case of operation of an instantaneous release) but at least up to the value  specified in table 3.

table 11 (see 8.3.2.2.4 and 8,3.2,2.5),

NOTE 2 Attention is drawn to the different requirements for the minimum required percentage of lc~ for utilization categories A and B, in accordance with table 1.

NOTE 3 A circuit-breaker of utilization category A may have an intentional short-time delay provided for selectivity under conditions other than those of short circuit, with a short-time withstand current less than that according to table 3. In that case, the tests include test sequence IV (see 8.3.6) at the assigned short-time

 
 
Hager    
•Ref:Electricians handbook courtesy of Larson and Toubro - India: 

IEC classifies MCBs into three category depending upon their “Quality of current
limiting” & let through energy of a circuit breaker on short circuits. Permissible let to energy values for circuit breakers with rated current up to end including 16A as per

EN60898 are:
Class 1 No limitation
Class 2 290 kA²S
Class 3 84 kA²S -

*All Hager mcb are class 3

 

   

 

Where must it be installed? 

 

south Africa

SANS10142: 6.7.1.1

Europe +

IEC 60364

 

USA+

UL489

UL1077

 

Canada


CSA c22.2 No 5.02CSA c22.2 No 235-04

 

  china

GB 14048-2

6.7.2.2 Overload must be installed at point of conductor reduction OR - with a switch/disconnector OR earth-leakage unit that requires overload protection.

UNLESS

The over current device can sit anywhere in the cable as long as no connections to/from it

AND

entire length protected against shorts circuit OR

cable shorter then 5mtrs

not near flammable materials

not likely to cause humans harm

I spent a lot of time trying to get to grips with this - I get this feeling this commission could not get consensus the matter of "anywhere in the cable"...thus the strange additions. Flammable and human safety? Really?

Now the challenge: Overload unit can be anywhere in the cable but the whole cable must be short circuit protected? HOW?

Mechanical protection or another electrical component?

Are we confusing motor overload protection with cable / reticulation protection here?

G-2 CASES WHERE SHORT-CIRCUIT PROTECTION DOES NOT NEED TO BE PLACED AT THE ORIGIN OF BRANCH CIRCUIT

With reference to 4.4.5.2.1and Fig. G.1, short-circuit protective device P 2may be moved up to 3 m from the origin (O) of the branch circuit (S2) provided that there is no other connection or socket-outlet on this length of the branch circuit, and in the case of 4.4.5.2.1
the risk of short-circuit, fire and danger to persons is reduced to a minimum for this length.

but:

4.4.4.2 Position of devices for overload protection
4.4.4.2.1 A device ensuring protection against overload shall be placed at the point where a change, such as a change in cross-sectional area, nature, method of installation or in constitution,
causes a reduction in the value of current-carrying capacity of the conductors, except where
4.4.3.2.2and 4.4.3.3 apply.

4.4.4.2.2 The device protecting the conductor against overload may be placed along the run of that conductor if the part of the run between the point where a change occurs (in cross-sectional area, nature, method of installation or constitution) and the position of the protective device has neither branch circuits nor socket-outlet circuits and fulfils at least one of the following two conditions:
a) it is protected against short-circuit current in accordance with the requirements stated in 4.4.5;
b) its length does not exceed 3 m, it is carried out
in such a manner as to reduce the risk of shortcircuit to a minimum, and it is installed in such a manner as to reduce to a minimum the risk of
fire or danger to persons (see also 4.4.5.2.1).
NOTE: For installation according to a) see Figure F.1.
For installation according to b) see Figure F.2.

       
           
6.7.2.3The overload protective device may be installed at any point in the conductor run that it protects, provided that

a) there is no branch circuit or socket-outlet between the point where there is a reduction in the conductor's current-carrying capacity and the point where the device is installed, and


b) the entire length of the conductor is protected against short-circuit, or
 

c) the conductor is
1) of length not exceeding 5 m,
2) so installed as to minimize the risk of overload or fault in its operating condition,
3) not near flammable materials, and
4) not likely to cause harm to a person in the event of a fault

         
Now short circuit protection is as plain and simple as "installed at the point of reduction" - as it should be!

6.7.3.2

 

AND SHORT CIRCUITS?

4.4.5.2 Position of devices for short-circuit protection A device ensuring protection against short-circuit shall be placed at the point where a reduction in the cross-sectional area of the conductors or another change causes a change to the current-carrying capacity of the conductors, except where 4.4.5.2.1, 4.4.5.2.2or 4.4.5.3 applies.
4.4.5.2.1 The various cases stated in the following sub clause shall not be applied to installations situated in locations presenting a fire risk or risk of explosion and where special rules for certain
locations specify different conditions. The device for protection against short-circuit may be placed other than as specified in 4.4.4.2, under the following conditions.

In the part of the conductor between the point of reduction of cross-sectional area or other change and the position of the protective device there shall be no branch circuits nor socket-outlet circuits
and that part of the conductor shall:
a) not exceed 3 m in length, and
b) be installed in such a manner as to reduce the risk of a short-circuit to a minimum,

and so forth and so forth...

 

       

...

 

Omitting fault current protection device

IEC 60364  
4.4.4.3 Omission of devices for protection against overload
The various cases stated in this sub-clause shall not be applied to installations situated in locations
presenting a fire risk or risk of explosion or where the requirements for special installations and
locations specify different conditions.

4.4.4.3.1 General Devices for protection against overload need not be provided:
a) for a conductor situated on the load side of a change in cross-sectional area, nature, method of
installation or in constitution, that is effectively protected against overload by a protective
device placed on the supply side;


b) for a conductor that is not likely to carry overload current, provided that this conductor is
protected against short-circuit in accordance with the requirements of 4.4.4 and that it has neither branch circuits nor socket-outlets;


c) at the origin of an installation where the distributor provides an overload device and agrees that it affords protection to the part of the installation between the origin an d the main distribution point of the installation where further overload protection is provided.


d) for circuits for telecommunications, control, signalling and the like.
NOTE: For installations according to a), b) and d), see Fig. F.3.

 
   
   

 

 

Relevant standards and circuit breakers:

PS: This is a reference based on manufacturer material referring to the different standards - Excuse if you are specialist and find some discrepancy...just let us know - for this is always a work in progress we would be a happy to oblige.

  UL ANSI NEC CSA

 

IEC
Genl

 

  Articles:

210 - Branch circuits

215 - Feeders

240 - Overcurrent Protection

430 - Motors, Motor Circuits, and Controllers
 controllers, and m

   
MCB

UL1066 - LV AC and DC CB in Enclosures

 

- ANSI C37.13: IEEE Standard for Low-Voltage AC Power Circuit Breakers Used in Enclosures

- ANSI C37.16: Low-Voltage Power Circuit Breakers and AC Power Circuit Protectors.

Preferred Ratings, Related Requirements, and Application Recommendations

- ANSI C37.17: American National Standard for Trip Devices for AC and General

Purpose DC Low Voltage Power Circuit Breakers

   

IEC 60947-2 (circuit breaker design and manufacturing)

IEC 60364, § 434.5.1 (electrical distribution network).

bulletIEC 947-4 - Circuit breakers with motor protective characteristics.

 

 

MCCB UL 489 - NEC -Branch circuit protection. MCCB.

UL 489: Molded-Case Circuit Breakers, Molded-Case Switches and Circuit Breaker Enclosures

UL 489 MCCB: MCS(Molded Case Switches) & Circuit Breaker Enclosures.

bulletUL 489A - Branch circuit protection DC circuit breaker short circuit protection in communications equipment.
bulletUL1077 - Used in conjunction with CB for supplementary external device protection.
bulletBranch circuit protection.
bulletUL1077 - Used in conjunction with CB for supplementary external device protection.
bullet 
bulletUL486- evaluation of lugs connection in field wiring this includes items under UL489. 
bullet 

 

 

    CSA C22.2 No. 5. 5-02 - CEC - Canadian -

 

CSA C22.2 No.235 - Used in conjunction with CB for supplementary external device protection.

 
ACB          
 
 
 

 

Definitions:

 

 

Analysis of a short circuit:-

The short-circuit current reaches its peak value after a quarter of the sinusoidal period, which is 5 milliseconds for 50Hz supply (4.2ms in the case of 60Hz as in the USA), assuming that the current is symmetrical, i.e. initiated at a current zero. This is to be prevented.

 

 

bxc

Coordination/Cascading/Backup protection

 

And lets dig deeper according to what standards say:

 

IEC 60947-2.2003

 

     
   

 

 

 

he obvious is that the information all provided by manufacturer and the components comply to relevant standards.

Ultimately: The maximum conditional short-circuit current (see 2.5.29 of Part 1) shall not exceed the rated ultimate short-circuit breaking capacity of the SC PD.

IEC 60947.2.2003

A.5 Verification of discrimination
Discrimination can normally be considered by desk study alone, i.e. by a comparison of the
operating characteristics of C1 and the associated SCPD, for example, when the associated
SCPD is a circuit-breaker (C2) provided with an intentional time-delay,


The manufacturers of both the C1 and the SCPD shall provide adequate data concerning the relevant operating characteristics so as to permit Is to be determined for each individual
association.

In certain cases, tests at Is are necessary on the association, for example
— when C1 is of the current-limiting type and C2 is not provided with an intentional time-delay;
— when the opening time of the SCPD is less than that corresponding to one half-cycle,
To obtain the desired discrimination when the associated SCPD is a circuit-breaker, an
intentional short-time delay may be necessary for C2.


Discrimination may be partial (see figure A.4) or total up to the rated short-circuit breaking
capacity Icu (or Ics) of C1. For total discrimination, the non-tripping characteristic of C2 or
the pre-arcing characteristic of the fuse shall lie above the tripping (break-time) characteristic
of C1.
Two illustrations of total discrimination are given in figures A.2 and A.3.

A.6 Verification of back-up protection


A.6.1 Determination of the take-over current: -Compliance with the requirements of A.3,2 can be checked by comparing the operating characteristics of Cl and the associated SCPD for ail settings of Cl and, if applicable, for all
settings of C2.

A.6.2 Verification of back-up protection
a) Verification by tests.
Compliance with the requirements of A.3.3 is normally verified by tests in accordance with
A.6.3. In this case, all the conditions for the tests shall be as specified in 8.3.2.6 with the
adjustable resistors and inductors for the short-circuit tests on the supply side of the
association.


b) Verification by comparison of characteristics
In some practical cases and where the SCPD is a circuit-breaker (see figures A,4 and A.5),
it may be possible to compare the operating characteristics of Cl and of the associated
SCPD, special attention being paid to the following:
– the Joule integral value of C1 at its Icu and that of the SCPD at the prospective current
of association;
– the effects on C1 (e.g. by arc energy, by maximum peak current, cut-off current) at the
peak operating current of the SCPD.

In some practical cases and where the SCPD is a circuit-breaker (see figures A,4 and A.5),
it may be possible to compare the operating characteristics of Cl and of the associated
SCPD, special attention being paid to the following:
– the Joule integral value of Cl at its /CU and that of the SCPD at the prospective current
of association;
– the effects on Cl (e.g. by arc energy, by maximum peak current, cut-off current) at the
peak operating current of the SCPD.
The suitability of the association may be evaluated by considering the maximum total
operating I2t characteristic of the SCPD, over the range from the rated short-circuit breaking
capacity Icu(or Ics) of C1 up to the prospective short-circuit current of the application, but not
exceeding the maximum let-through I2t of C1 at its rated short-circuit breaking capacity or
other lower limiting value stated by the manufacturer.
NOTE Where the associated SCPD is a fuse, the validity of the desk study is limited up to Icu of

A.6.3 Tests for verification of back-up protection
If C1 is fitted with adjustable over-current opening releases, the operating characteristics shall
be those corresponding to the minimum time and current settings,
If C1 can be fitted with instantaneous over-current opening releases, the operating
characteristics to be used shall be those corresponding to Cl fitted with such releases,
If the associated SCPD is a circuit-breaker (C2) fitted with adjustable over-current opening
releases, the operating characteristics to be used shall be those corresponding to the
maximum time and current settings.
If the associated SCPD consists of a set of fuses, each test shall be made using a new set of
fuses, even if some of the fuses used during a previous test have not blown

Where applicable, the connecting cables shall be included as specified in 8.3.2.6.4 except that,
if the associated SCPD is a circuit-breaker (C2), the full length of cable (75 cm) associated with
this circuit-breaker may be on the supply side (see figure A.6).
Each test shall consist of a O–t–CO sequence of operations made in accordance with 8.3.5 of
this standard, ‘whether at /Cu or /C~, the CO operation being made on Cl.
 

A test is made with the maximum prospective current for the proposed application, This shall
not exceed the rated conditional short-circuit (see 4.3.6.4 of Part 1),
 

A further test shall be made at a value of prospective current equal to the rated short-circuit
breaking capacity /Cu (or /CS) of Cl, for which test a new sample Cl may be used, and also, if
the associated SCPD is a circuit-breaker, a new sample C2.

a) if the associated SCPD is a circuit-breaker (C2):
– either both Cl and C2 shall trip at both test currents, no further tests then being
required.
 

This is the general case and provides back-up protection only.
– or C1 shall trip and C2 shall be in the closed position at the end of each operation, at
both test currents, no further tests then being required,
This requires that the contacts of C2 separate momentarily during each operation. In this
case restoration of the supply is provided, in addition to back-up protection (see note 1 to
figure A.4), The duration of interruption of supply, if any, shall be recorded during these
tests.
– or C1 shall trip at the lower test current, and both C1 and C2 shall trip at the higher test
current.
This requires that the contacts of C2 separate momentarily at the lower test current.
Additional tests shall be made at intermediate currents to determine the lowest current at
which both C1 and C2 trip, up to which current restoration of supply is provided. The
duration of interruption of supply, if any, shall be recorded during these tests.

– or C1 shall trip at the lower test current, and both C1 and C2 shall trip at the higher test
current.
This requires that the contacts of C2 separate momentarily at the lower test current.
Additional tests shall be made at intermediate currents to determine the lowest current at
which both C1 and C2 trip, up to which current restoration of supply is provided. The
duration of interruption of supply, if any, shall be recorded during these tests.
b) if the associated SCPD is a fuse (or a set of fuses):

In the case of a single-phase circuit at least one fuse shall blow;
— in the case of a multi-phase circuit either two or more fuses shall blow, or one fuse shall
blow and C1 shall trip.

A.6.4 Results to be obtained
Subclause 8.3.4.1.7 of Part 1 applies.
Following the tests, C1 shall comply with 8.3,5.3 and 8.3.5.4
In addition, if the associated SPCD is a circuit-breaker (C2), it shall be verified, by manual
operation or other appropriate means, that the contacts of C2 have not welded.

 

 

     
 

 

     

...

 

Up side down circuit breakers

SANS 2012 NEC  

6.8.2.3

Circuit-breakers, disconnectors and switch-disconnectors shall not be mounted upside down.

Who would want to do this anyway...zimzum.

Horizontal mounting is allowed unless specifically prohibited by the manufacturer.

 

Any deviation from the convention of connecting line to the top and load to the bottom of switchgear is not recommended. Reverse connection is allowed only if

a) it is specifically allowed by the manufacturer,

b) "load" and "line" are so marked that they are clearly visible during

maintenance, and

c) any contradictory marking is not visible after installation.

NEC404.7 inferred so,  

 

 

 

 

 

AC circuit breakers and power factor:

Standard relationship between short-circuit breaking and making capacities and related power factor.

 

Table 2 -ratio n between short-circuit making capacity and short-circuit
breaking capacity and related power factor (for a.c. circuit-breakers)

Short-circuit breaking capacity I kA r.m.s. Power factor I Minimum value required for n

n=(short - circuit making capacity/short - circuit breaking capacity)

4,5 <= / <= 6
6 <= / <=10
10 <= / <= 20
20 <= I <= 50
50 <= /
0,7
0,5
0,3
0,25
0,2
1,5
1,7
2,0
2,1
2,2
     
     
     

NOTE: For values of breaking capacity lower than 4,5 kA, for certain applications, see table 11 for the power
factor.

The rated short-circuit making and breaking capacities are only valid when the circuit-breaker
is operated in accordance with the requirements of 7.2.1,1 and 7.2. i.2.

For special requirements, the manufacturer may assign a value of rated short-circuit making
capacity higher than that required by table 2. Tests to verify these rated values shall be the
subject of agreement between manufacturer and user.

 
 

 

MCCB range

ABB

Tmax - 15 to 3000Amps,

       
         
         
         

 

ACB (low voltage Power circuit breakers)

ABB:

Emax: 400 to 5000A

but I saw the SACE can go to 6300A

 

       
         
         
         

 

Online references:

http://www.electrical-installation.org/enwiki/Fundamental_characteristics_of_a_circuit-breaker

http://www.electrical-installation.org/enwiki/Fundamental_characteristics_of_a_circuit-breaker

http://www.terasaki.co.uk/tembreak2/application note_mccb.htm

 
Drawing notations:

 

 

Standards references:

 

bulletEN 60947-2
bulletIEC 947-4 - Circuit breakers with motor protective characteristics.

______________==========_____________

bulletUL 489 - NEC -Branch circuit protection. MCCB.
bulletUL 489A - Branch circuit protection DC circuit breaker short circuit protection in communications equipment.
bulletUL1077 - Used in conjunction with CB for supplementary external device protection.
bulletCSA C22.2 No. 5. 5-02 - CEC - Canadian - Branch circuit protection.
bulletUL1077 - Used in conjunction with CB for supplementary external device protection.
bulletCSA C22.2 No.235 - Used in conjunction with CB for supplementary external device protection.
bulletUL486- evaluation of lugs connection in field wiring this includes items under UL489. 

______________==========_____________

VC8035 -

VC8036 -