
| |
Basic definitions:
1.2.3. Load-break switch
The load break switch is a mechanical switching device
capable of making, carrying and breaking currents under normal circuit
conditions which may include specified operating overload conditions and also
carrying for a specified time
currents under specified abnormal circuit conditions such as those of
shortcircuit.
A load switch may be capable of making but not breaking, short-circuit currents
(IEC 947-1). It is capable of carrying (high short-time withstand capability)
but not breaking the short-circuit currents.
1.2.4. Disconnector/isolator:-
A mechanical switching device which, in the open
position, complies with the requirements specified for isolating function (IEC
947-1). The isolating device must disconnect the supply
voltage from the whole installation or from part of the installation, thereby
for ensuring safety, the whole installation or part of the installation must be
completely isolated from all sources of electrical energy. The important factor
here is the isolating distance. The isolation of pole to pole or
between the incoming and outgoing terminals must be assured, be it with a
visible isolating gap or with the help of appropriate internal constructive
measures (mechanical interlocking device).
A device meets the requirements of isolating function in accordance with the
IEC 947-1 if it provides an isolating distance in the "OFF" position so that the
prescribed dielectric strength between the open contacts of the main current
path of the switch is assured.
Additionally, it must be provided with an indicator which shows the position of
the moving contacts. This switching position
indicator must be mechanically connected to the operating mechanism in a
reliable and robust way. The operating mechanism itself may serve the
purpose of the switching position indicator provided in the "TRIP" position it
indicates the position "OFF" only when all the moving contacts are in the "OFF"
position. A disconnector is capable of opening and
closing a circuit when either a negligible current is broken or made, or when no
significant change in the voltage across the terminals of each of the poles of
the disconnector occurs. It is also capable of
carrying currents under normal circuit conditions and carrying for a specified
time currents under abnormal conditions such as those of short-circuit.
Main switch:-
Every electrical equipment must be provided with a manual
main switch which completely disconnects the equipment from the supplies so that
cleaning, maintenance or repairs can be carried out or if the machine is to be
taken out of service for a longer period of time.
A main switch must meet the
requirements of a switch-disconnector in accordance with the IEC 947-3 (load
switch with isolating function - see above). It must at least meet the
requirements of the utilisation category AC-23.
A main switch is manually operated and must have only one "OFF" and one "ON"
position, which are to be clearly marked with O and I respectively.
A main switch must have a visible isolating gap or an unambiguous indication of
the "OFF" position of the switch as soon as the gap between the contacts has
reached the prescribed isolating distance in accordance with the IEC 947-3.
As long as the main switch do not serve the purpose of an emergency OFFswitch at
the same time, it may not have a red operating handle.
It must be possible to lock-out the handle in the
OFF-position (as for example with a padlock).
If necessary, it must be possible to interlock the main
switch with a door with the help of an interlocking device.
A main switch placed within the reach of an operator must fulfil the
requirements of an emergency OFF-switch.
Emergency OFF-switch
In the case of a danger to persons or machines, the part
in danger or the whole machine itself must be quickly isolated from the supply
and brought to stand-still with the help of an emergency OFF-switch.
The emergency OFF-switch must be capable of interrupting the locked-rotor
current of the largest motor connected to it and added to it, the sum of the
rated currents of all the other loads connected to the same switch.
The contacts must fulfil the isolating function.
The operating handle or button must be clearly visible by the operator from his
operating position and must be located within his easy reach.
The operating handle or button must be coloured red. The background or mounting
surface must be coloured yellow so that the handle or the button clearly stands
out against the background.
The emergency OFF-switch must not disconnect an electrical circuit, which when
disconnected may lead to danger to persons or to machines.
It must be capable of carrying continuously the sum of the rated currents of all
the loads connected to it.
|
STANDARDS and references:
Why is the plug socket rating 16Amp and not 20Amp?
Why for a plug(feeder) circuit the circuit
breaker is 20Amp rated, the wire size is normally 2.5mm, but the sockets in
that circuit are 16Amps! What's up with that?
SANS |
|
|
|
6.15.3 Single-phase circuits that
only supply socket-outlets rated at 16A
Single-phase
circuits that only supply socket-outlets rated at not more than 16 A,
a) shall have overcurrent protection;
b) shall use conductors that are rated at not less than 16 A;
c) shall, if the circuit
protection is rated at more than 20 A, use only protected
socket-outlets, with, as far as is practicable, discrimination between
the protective devices for the circuit and the protective devices
associated with the socket-outlets.
The protective
device of a protected socket-outlet shall
1) have a fixed rated current that does not exceed the rating of the
socket-outlet,
2) be mounted next to the socket-outlet that it protects,
3) provide protection against overload currents,
4) provide protection against short-circuit currents, unless
short-circuit protection is provided by a separate device, for example
on the distribution board,
5) if it needs the protection of a back-up short-circuit device, be
marked with the required or maximum rating of the back-up
device,
6) if it protects more than one socket-outlet, be so installed that all
the socket-outlets are connected in parallel, have the same rated
current, and are mounted next to the device, and
7) if it is a circuit-breaker, comply with the requirements of 6.8.2.
NOTE In the interest of safety, the use of the building, the
convenience of the occupants and the possibility of heating and cooling
equipment being connected to socket-outlets, should be considered when
the number and position of points of
consumption are being determined.
|
|
|
|
|
|
|
|