ElectroStores
Home Up Switches Relays Circuitbreakers Automation Metering Sensors Controllers and modules Standards Acronyms and definitions Training Control and Safety About us

 

Up

----------------------------=========================------------------------

 

PURPOSE OF EARTHING

In order to avoid the risk of serious electric shock, it is important to provide a path for earth leakage currents to operate the circuit protection, and to endeavour to maintain all metalwork at the same potential. This is achieved by bonding together all metalwork of electrical and non-electrical systems to earth.

 
 
EARTHING SYSTEMS
Various excepted methodologies of electrical supply exist around the world but they all serve one common purpose – The phase (live) supply relationship to the earth-mass determines how safe we are from electrocution…

 
SANS adopted the IEC standards and recommendations. IEC IEC 60364  
In general the South African reticulation is based on TN-S system

A peculiar acronym identify the basic systems. Seems to be based on the French lingo.

When these letters are grouped, they form the classification of a type of system.
The first letter denotes how the supply source is earthed.
The second denotes how the metalwork of an installation is earthed. The third and fourth indicate the functions of neutral and protective conductors.

bullet The two + 1 +1 code
bullet The First Letter indicates how the Earthing is done on Source side (Generator / Transformer).
bullet The Second Letter indicates how the Earthing is done on Device side (place where electricity is consumed at customer premises).
bullet3rd and sometimes 4th letters:
bulletC - combined
S - separate.
CS - Combined in supply separated in installation:

T – (French word “Terre” meaning Earth) – It means direct connection of a point to earth

I – It means that either no point is connected to Earth or it is connected via high impedance

N – It means that there is direct connection to neutral at the source of installation which is in turn connected to the ground

Based on a combination of these three letters, there are three families of Earthing arrangements proposed by IEC as below:

bullet TN Network
bullet TT Network
bullet IT Network
bulletSo you can have:
bulletThere are three sub-types of TN networks as below:
TN-S
TN-C
TN-C-S
TN-S: In this, separate conductors for Protective Earth (PE) and Neutral run from Consumer’s electrical installation till the source. They are connected together only at the power source.

 

These have been designated in the IEE Regulations using the letters: T, N, C and S. These letters stand for:
 
T - Terre (French for earth) and meaning a direct connection to earth.
N - neutral
 

---------============-------

For the UK: BS 7671: 2008 defines or lists the types of system earthing in
Part 2 – (definitions)
and these are also defined in BS 7430: 1998.

-----------===========---------
PE – Acronym for “Protective Earth” – is the conductor that connects the exposed metallic parts of the consumer’s electrical installation to the ground.
 


NB: IT Network


In IT type of earthing system, there is either no connection to earth at all, or it is done via a high impendence earthing connection.

About “ IT ” :
We should also mention to the following :
1- If the connection of the transformer is “ ∆ ” ( no neutral point ) we can connect one phase to earth via high impedance.
2- Two main types of “ IT ” that are :
 – IT with distributed Neutral
 – IT without distributed Neutral.
3- With this
Earthing system, It’s absolutely necessary to use special devices called “ Insulation Monitoring Devices ” to detect and indicate any insulation fault .

bullet

----------==========------------

 

-------TT SYSTEM------

-----===========-------------

 

A TT system has a direct connection to the supply source to earth and a direct connection of the installation metalwork to earth. An example is an overhead line supply with earth electrodes, and the mass of earth as a return path as shown below.

 
Note that only single-phase systems have been shown for simplicity.

TT Network
In TT type of earthing system, consumer employs its own local earth connection in the premises, which is independent of any earth connection at source side.
This type of earthing is preferred in telecommunication applications, because this system is free of any high or low frequency noise that comes through neutral wire connected to the equipment.
 

The TT method is used mostly in country areas with overhead transmission lines.

In contrast to the TN-S system there is no metallic path from the consumer's terminals back to the sub-station transformer secondary windings.
Because the earth path may be of high resistance, a residual current circuit-breaker (R.C.C.B.) is often fitted so that if a fault current flows in the earth path then a trip disconnects the phase supply.
For protection against indirect contact in domestic premises, every socket outlet requires an RCCB with a maximum rated current of 30mA.

-----------=======--------

– About “ TT ” :
Also, it’s better to add :
– As we can use many independent
Earthing points at consumers side only, this system is approximately used all around the world in LV Distribution Networks to supply Housings and buildings.
 

--------===============-----------

In TN type of earthing system, one of the points of the source side (Generator or Transformer) is connected to earth. This point is usually the star point in a three phase system. The body of the connected electrical device is connected to earth via this earth point on the source side. See fig. below which depicts this:
 

----------===========--------------
 

TN-S SYSTEM:

A TN-S system has the supply source directly connected to earth, the installation metalwork connected to the neutral of the supply source via the lead sheath of the supply cable, and the neutral and protective conductors throughout the whole system performing separate functions.


The resistance around the loop P-B-N-E should be no more than 0.8 ohms.

---------------============-------------

The TN-S system of wiring uses the incoming cable sheath as the earth return path and the phase and neutral have separate conductors. The neutral is then connected to earth back at the transformer sub-station.
Remember in TN-S, the T stands for earth (terre), N for neutral and S denotes that the protective (earth) and neutral conductors are separate.
 

 

 
--------=========---------


TN-C: In this, there is a combined conductor called PEN (Protective Earth-Neutral) which is connected to earth at the source.
      

– About “ TN-C ” :
The following remark should be also mentioned :
– If the supply of a load is “ 3Ph + N ” and we will use only “ 1 cable of PEN ” between the network and that load, the connection of PEN should be done as follow “ the PEN cable should be firstly connected to the earth point at Load, then to the neutral point ”.

 

--------==========---------

TN-C-S SYSTEM:

A TN-C-S system is as the TN-S but the supply cable sheath is also the neutral, i.e. it forms a combined earth/neutral conductor known as a PEN (protective earthed neutral) conductor.
The installation earth and neutral are separate conductors.
This system is also known as PME (protective multiple earthing).

The resistance around the P-B-N-N loop should be less than 0.35 ohms.

--------------=============------------


TN-C-S: In this type of earthing, part of the system uses a combined PEN conductor for earthing, whereas for remaining part of the system uses separate conductor for PE and N.
Usually, the combined PEN conductor is used near the source of the system.

 

------------========------------

The TN-C-S system has only two conductors in the incoming cable, one phase and the other neutral. The earth is linked to the neutral at the consumer unit. The neutral therefore is really a combined earth/neutral conductor hence the name PME(Protective Multiple Earthing).

------------==============-------

– About “ TN-C-S ” :
It’s mentioned that “ Usually, the combined PEN conductor is used near the source of the system ”, but it’s better to say :
1- For the big networks where the installed power is big or too big, we use
TN-C at the 1st and maybe also at the 2nd levels of the network, then we use TN-S.
2- By this way we can decrease the installation’s costs for these 2 levels.
3- We can’t never ever use firstly “
TN-S ” then “ TN-C ”.
 

 

---------------================---------------

Country Specific Earthing Standards thanks to or copy this trackback: http://engineering.electrical-equipment.org/iec-standard/types-of-earthing-as-per-iec-standards.html/trackback from your own site.

UK – Uses Protective Multiple Earthing (PME) – which is a form of TN-C-S type of earthing
Australia / New Zealand – Also uses TN-C-S type of earthing know as Multiple Earth Neutral (MEN) system
USA / Canada Uses TN-C for the feed from Transformer but uses TN-C-S within the structure at customer premises
France / Japan / Denmark Uses TT type of earthing and customer must make its own arrangement for its own earthing connection

-----------===========------------
 Points to consider in BS 7671 regulations:



Earth electrodes:

BS 7671 lists a wide range of earth electrodes recognised by wiring regulations, including earth rods, earth plates and underground structural metalwork.

The single most importance deciding factor in which type of electrode to use is resistance capacity of the soil in the ground.

Ideally it should virgin, undisturbed ground, and the effects of soil drying, freezing, and the potential for corrosion, should also be considered, with tests carried out in the worst weather conditions.
 

Sizing of Circuit Protective Conductors
Several factors must be considered when working out the required size of circuit protective conductor. A minimum cross–sectional area of 2.5mm2 copper is necessary for any separate circuit protective conductor, meaning one which is not part of a cable or created by/contained inside a wiring enclosure.
 

Earthing Conductors:
Earthing conductors defined by BS 7671 as a protective conductor connecting the main earthing terminal of an installation to an earth electrode must be sized appropriately, especially if partially buried. They must be made from suitable material and protected against corrosion and mechanical damage. The appropriate size is determined in the same way as for a circuit protective conductor, except for with buried earthing conductors, in which case check BS 7671 for further guidelines. In addition, earthing conductors for a TN–C–S supply should not be smaller than the main bonding conductors.
 

Special Locations:
These are locations where extra precautions need to be taken. For example PMEs cannot be used for caravans or boats as the combined neutral and protective conductor is not allowed to be connected electrically to any metalwork in them, whilst a TT system is recommended for hazardous areas such as petrol stations, and should be accompanied by the supply of a separate electrode and circuit breaker such as an RCD, in order to ensure that the earthing in the petrol filling area and the PMP earth of the distribution network are separated.

 
 

 

 

 

--------------------------------=======================------------------------