NEC circuit
breaker motor protection notes:
VII. Service Equipment —
Overcurrent Protection
230.90 Where Required, Each ungrounded service conductor shall
have overload protection.
(A) Ungrounded Conductor. Such protection shall be provided by an over
current device in series with each ungrounded
service conductor that has a rating or setting not higher than the allowable
ampacity of the conductor.
A set of fuses shall be considered all the fuses required to protect all
the ungrounded conductors of a circuit.
Single-pole circuit breakers, grouped in accordance with 230.71(B), shall
be considered as one protective device.
230.71 Use of up to 6 single phase
cb or isolators with handles locked together can be used on a multiphase
circuit
Exception No. 1: For motor-starting currents, ratings that comply with
430.52, 430.62, and 430.63 shall be permitted.
Exception No. 2: Fuses and circuit breakers with a rating or setting that
complies with 240.4(B) or (C) and 240.6
shall be permitted.
Exception No. 3: Two to six circuit breakers or sets of fuses shall be
permitted as the overcurrent device to provide the overload protection. The
sum of the ratings of the circuit
breakers or fuses shall be permitted to exceed the ampacity of the service
conductors, provided the calculated load does not
exceed the ampacity of the service conductors.
Exception No. 4: Overload protection for fire pump supply conductors shall
comply with 695.4(B)(2)(a).
Exception No. 5: Overload protection for 120/240-volt,3-wire,
single-phase dwelling services shall be permitted in
accordance with the requirements of 310.15(B)(6).
-------=========-------
230.91 cb Location.
The service overcurrent device shall be an integral part of the service
disconnecting means or shall be located immediately adjacent thereto.
--------========
430.32 Continuous-Duty Motors.
* Any motor application shall be considered to be for
continuous duty unless the nature of the apparatus it drives is such that
the motor cannot operate continuously with load under any condition of use.
(A)
More Than 1 Horsepower.
Each motor used in a continuous duty application and rated more than 1 hp
shall be protected against overload by one of the means in 430.32(A)(1)
through (A)(4).
(1) Separate Overload
Device.
A separate overload device that is responsive to motor current.
This device shall be selected to trip or shall be rated at no more than
the following percent of the motor nameplate full-load current rating:
Motors with a marked service factor 1.15 or greater: 125%
Motors with a marked temperature rise 40°C or less: 125%
All other motors: 115%
(2) Thermal
Protector.
A thermal protector integral with the motor, approved for use with the
motor it protects on the basis that it will prevent dangerous overheating of
the motor due to overload and failure to start.
The ultimate trip current of a thermally protected motor shall not exceed
the following percentage of motor full-load current given in Table 430.248,
Table 430.249, and Table 430.250:
Motor full-load current 9 amperes or less: 170%
Motor full-load current from 9.1 to, and including, 20 amperes: 156%
Motor full-load current greater than 20 amperes: 140%
If the motor current-interrupting device is separate from the motor and
its control circuit is operated by a protective device integral with the
motor, it shall be arranged so that the opening of the control circuit will
result in interruption of current to the motor.
(3) Integral with
Motor. A protective device integral with a motor that will protect the
motor against damage due to
failure to start shall be permitted if the motor is part of an approved
assembly that does not normally subject the motor to overloads.
(4) Larger Than 1500
Horsepower. For motors larger than 1500 hp, a protective device having
embedded temperature
detectors that cause current to the motor to be interrupted when
the motor attains a temperature rise greater than marked
on the nameplate in an ambient temperature of 40°C.
========
430.32( B)
One Horsepower or Less,
Automatically Started.
Any motor of 1 hp or less that is started automatically
shall be protected against overload by one of the following means.
(1) Separate
Overload Device. By a separate overload device following the
requirements of 430.32(A)(1).
For a multispeed motor, each winding connection shall be considered
separately. Modification of this value shall be
permitted as provided in 430.32(C).
(2) Thermal Protector.
A thermal protector integral with the motor, approved for use with the
motor that it protects
on the basis that it will prevent dangerous overheating of the motor due
to overload and failure to start. Where the
motor current-interrupting device is separate from the motor and its
control circuit is operated by a protective device
integral with the motor, it shall be arranged so that the opening of the
control circuit results in interruption of current to the motor.
(3) Integral with
Motor. A protective device integral with a motor that protects the motor
against damage due to failure to start shall be permitted (1) if the motor
is part of an approved assembly that does not subject the motor to
overloads, or (2) if the assembly is also equipped with other safety
controls (such as the safety combustion controls on a domestic oil burner)
that protect the motor against damage due to failure to start. Where the
assembly has safety controls that protect the motor, it shall be so
indicated on the nameplate of the assembly where it will be visible after
installation.
(4) Impedance-Protected.
If the impedance of the motor windings is sufficient to prevent overheating
due to failure to start, the motor shall be permitted to be protected as
specified in 430.32(D)(2)(a) for manually started motors if the motor is
part of an approved assembly in which the motor will limit itself so that it
will not be dangerously overheated.
Informational Note: Many ac motors of less than 1⁄20 hp, such as clock
motors, series motors, and so forth, and also some larger motors such as
torque motors, come within this classification. It does not include
split-phase motors having automatic switches that disconnect the starting
windings
430.32(C)
Selection of Overload Device.
Where the sensing element or setting or sizing of the overload device
selected in accordance with 430.32(A)(1) and 430.32(B)(1) is not sufficient
to start the motor or to carry the load, higher size sensing elements or
incremental settings or sizing shall be permitted to be used, provided the
trip current of the overload device does not exceed the following percentage
of motor nameplate full-load current rating:
Motors with marked service factor 1.15 or greater 140%
Motors with a marked temperature rise 40°C or less 140%
All other motors 130%
If not shunted during the starting period of the motor as provided in
430.35, the overload device shall have sufficient time delay to permit the
motor to start and accelerate its load.
Informational Note: A Class 20 or Class 30 overload relay will provide a
longer motor acceleration time than a Class 10 or Class 20, respectively.
Use of a higher class overload relay may preclude the need for selection of
a higher trip
current.
(D) One Horsepower or Less,
Nonautomatically Started.
(1) Permanently Installed.
Overload protection shall be in accordance with 430.32(B).
(2) Not Permanently Installed.
(a) Within Sight from
Controller. Overload protection shall be permitted to be furnished by the
branch circuit short-circuit and ground-fault protective device;
such device, however, shall not be larger than that specified in Part IV
of Article 430.
Exception: Any such motor shall be permitted on a nominal 120-volt
branch circuit protected at not over 20 amperes.
(b) Not Within Sight from
Controller. Overload protection shall be in accordance with 430.32(B).
(E) Wound-Rotor Secondaries.
The secondary circuits of wound-rotor ac motors, including conductors,
controllers, resistors, and so forth, shall be permitted to be protected
against overload by the motor-overload device.
430.33 Intermittent and Similar Duty.
A motor used for a condition of service that is inherently short-time,
intermittent, periodic, or varying duty, as illustrated by Table 430.22(E),
shall be permitted to be protected against overload by the branch-circuit
short-circuit and ground-fault protective device, provided the protective
device rating or setting does not exceed that specified in Table 430.52.
Any motor application shall be considered to be for continuous duty
unless the nature of the apparatus it drives is such that the motor cannot
operate continuously with load under any condition of use.
430.35 Shunting During Starting Period.
(A) Non automatically Started.
For a non automatically started motor, the overload protection shall
be permitted
to be shunted or cut out of the circuit during the starting period of the
motor if the device by which the overload
protection is shunted or cut out cannot be left in the starting position
and if fuses or inverse time circuit
breakers rated or set at not over 400 percent of the full load current of
the motor are located in the circuit so as
to be operative during the starting period of the motor.
(B) Automatically Started.
The motor overload protection shall not be shunted or cut out during the
starting period if the
motor is automatically started.
Exception: The motor overload protection shall be permitted to be shunted
or cut out during the starting period on
an automatically started motor where the following apply:
(a) The motor starting period exceeds the time delay of available motor overload protective devices, and
(b) Listed means are provided to perform the following:
(1) Sense motor rotation and automatically prevent the shunting or cutout
in the event that the motor fails to
start, and
(2) Limit the time of overload protection shunting or cutout to less than
the locked rotor time rating of the protected
motor, and
(3) Provide for shutdown and manual restart if motor running condition is
not reached
430.36 Fuses — In Which Conductor.
Where fuses are used for motor overload protection, a fuse shall be
inserted in each ungrounded conductor and also in the grounded conductor if the
supply system is 3-wire, 3-phase ac with
one conductor grounded.
430.37 Devices Other Than Fuses — In Which
Conductor.
Where devices other than fuses are used for motor overload protection,
Table 430.37 shall govern the minimum allowable number and location of
overload units such as trip coils or relays.
430.38 Number of Conductors Opened by Overload
Device.
Motor overload devices, other than fuses or thermal protectors, shall
simultaneously open a sufficient number of ungrounded conductors to
interrupt current flow to the motor
430.39 Motor Controller as Overload Protection.
A motor controller shall also be permitted to serve as an overload device
if the number of overload units complies with Table 430.37 and if these
units are operative in both the starting and running position in the case of
a dc motor, and in the running position in the case of an ac motor.
430.40 Overload Relays.
Overload relays and other devices for motor overload protection that are
not capable of opening short circuits or ground faults shall be protected by
fuses or circuit breakers with ratings or settings in accordance with 430.52
or by a motor short-circuit protector in accordance with 430.52.
Exception: Where approved for group installation and marked to indicate
the maximum size of fuse or inverse time
circuit breaker by which they must be protected, the overload devices
shall be protected in accordance with this marking.
430.42 Motors on General-Purpose Branch Circuits.
Overload protection for motors used on general-purpose branch circuits as
permitted in Article 210 shall be provided as specified in 430.42(A), (B),
(C), or (D).
(A) Not over 1 Horsepower. One or more motors without individual overload
protection shall be permitted to be connected to a general-purpose branch
circuit only where the installation complies with the limiting conditions
specified in 430.32(B) and 430.32(D) and 430.53(A)(1) and (A)(2).
(B) Over 1 Horsepower. Motors of ratings larger than specified in
430.53(A) shall be permitted to be connected to general-purpose branch
circuits only where each motor is protected by overload protection selected
to protect the motor as specified in 430.32. Both the controller and the
motor overload device shall be approved for group installation with the
short-circuit and ground-fault protective device selected in accordance with
430.53
(C) Cord-and-Plug-Connected. Where a motor is connected to a branch
circuit by means of an attachment plug and a receptacle or a cord connector,
and individual overload protection is omitted as provided in 430.42(A), the
rating of the attachment plug and receptacle or cord connector shall not
exceed 15 amperes at 125 volts or 250 volts. Where individual overload
protection is required as provided in 430.42(B) for a motor or
motor-operated appliance that is attached to the branch circuit through an
attachment plug and a receptacle or a cord connector, the overload device
shall be an integral part of the motor or of the appliance. The rating of
the attachment plug and receptacle or the cord connector shall determine the
rating of the circuit to which the motor may be connected, as provided in
210.21(B).
(D) Time Delay. The branch-circuit short-circuit and ground fault
protective device protecting a circuit to which a motor or motor-operated
appliance is connected shall have sufficient time delay to permit the motor
to start and accelerate its load
430.43 Automatic Restarting.
A motor overload device that can restart a motor
automatically after overload tripping shall not be installed unless approved
for use with the motor it protects. A motor overload device that can restart
a motor automatically after overload tripping shall not be installed if
automatic restarting of the motor can result in injury to persons.
430.44 Orderly Shutdown.
If immediate automatic shutdown of a motor by a motor overload protective
device(s) would introduce additional or increased hazard(s)
to a person(s) and continued motor operation is necessary for safe
shutdown of equipment or process, a motor
overload sensing device(s) complying with the provisions of Part III of
this article shall be permitted to be
connected to a supervised alarm instead of causing immediate interruption
of the motor circuit, so that corrective action or an orderly shutdown can
be initiate
--------===
IV. Motor Branch-Circuit Short-Circuit and
Ground-Fault Protection
430.51 General.
Part IV specifies devices intended to protect the motor branch-circuit
conductors, the motor control apparatus, and the motors against overcurrent
due to short circuits or ground faults. These rules add to or amend the
provisions of Article 240.
The devices specified in Part IV do not include the types of devices
required by 210.8, 230.95, and 590.6.
The provisions of Part IV shall not apply to motor circuits rated over
600 volts, nominal.
Informational Note No. 1: For over 600 volts, nominal, see Part XI.
Informational Note No. 2: See Informative Annex D, Example D8.
430.52 Rating or Setting for Individual Motor Circuit.
(A) General. The
motor branch-circuit short-circuit and ground-fault protective device shall
comply with 430.52(B) and either 430.52(C) or (D), as applicable.
(B) All Motors. The
motor branch-circuit short-circuit and ground-fault protective device shall
be capable of carrying the starting current of the motor
(C)
Rating or Setting.
(1) In Accordance with
Table 430.52. A protective device that has a rating or setting not exceeding
the value calculated according to the values given in Table 430.52 shall be used.
Exception No. 1:Where the values for branch-circuit shortcircuit and
ground-fault protective devices determined by Table 430.52 do not correspond
to the standard sizes or ratings of fuses, nonadjustable circuit breakers,
thermal protective devices, or possible settings of adjustable circuit
breakers, a higher size, rating, or possible setting that does not exceed
the next higher standard ampere rating shall be permitted.
Exception No. 2: Where the rating specified in Table 430.52, or the
rating modified by Exception No. 1, is not suff ıcient
for the
starting current of the motor:
(a) The rating of a nontime-delay fuse not exceeding 600 amperes or a
time-delay Class CC fuse shall be permitted to be increased but shall in no
case exceed 400 percent of the
full-load current.
(b) The rating of a time-delay (dual-element) fuse shall be permitted to
be increased but shall in no case exceed
225 percent of the full-load current.
(c) The rating of an inverse time circuit breaker shall be permitted to
be increased but shall in no case exceed 400 percent for full-load currents
of 100 amperes or less or 300 percent for full-load currents greater than
100 amperes.
(d) The rating of a fuse of 601–6000 ampere classification shall be
permitted to be increased but shall in no case exceed 300 percent of the
full-load current.
Informational Note: See Informative Annex D, Example D8, and Figure
430.1.
(2) Overload Relay
Table. Where maximum branch-circuit short-circuit and ground-fault
protective device ratings are shown in the manufacturer’s overload relay
table for use with a motor controller or are otherwise marked on the
equipment, they shall not be exceeded even if higher values are allowed as
shown above.
(3) Instantaneous Trip
Circuit Breaker. An instantaneous trip circuit breaker shall be used only if
adjustable and if part of a listed combination motor controller having
coordinated motor overload and short-circuit and ground-fault protection in
each conductor, and the setting is adjusted to no more than
the value specified in Table 430.52.
Informational Note: For the purpose of this article, instantaneous
trip circuit breakers may include a damping means to accommodate a transient
motor inrush current without nuisance tripping of the circuit breaker.
Exception No. 1: Where the setting specified in Table 430.52 is not
suffıcient for the starting current of the motor, the setting of an
instantaneous trip circuit breaker shall be permitted to be increased but
shall in no case exceed 1300 percent of the motor full-load current for
other than Design B energy effıcient motors and no more than 1700 percent of
full-load motor current for Design B energy-effıcient motors. Trip settings
above 800 percent for other than Design B energyeffıcient motors and above
1100 percent for Design B energy effıcient motors shall be permitted where
the need has been demonstrated by engineering evaluation. In such cases, it
shall not be necessary to first apply an instantaneous-trip circuit breaker
at 800 percent or 1100 percent.
Informational Note: For additional information on the requirements for a
motor to be classified “energy efficient,” see NEMA Standards Publication
No. MG1-1993, Revision,Motors and Generators,Part 12.59.
Exception No. 2: Where the motor full-load current is 8 amperes or less,
the setting of the instantaneous-trip circuit breaker with a continuous
current rating of 15 amperes or less in a listed combination motor
controller that provides coordinated motor branch-circuit overload and
short-circuit and ground-fault protection shall be permitted to be increased
to the value marked on the controller
(4) Multispeed Motor.
For a multispeed motor, a single short-circuit and ground-fault protective
device shall be permitted for two or more windings of the motor, provided
the rating of the protective device does not exceed the above applicable
percentage of the nameplate rating of the smallest winding protected.
Exception: For a multispeed motor, a single short-circuit and
ground-fault protective device shall be permitted to be used and sized
according to the full-load current of the highest current winding, where all
of the following conditions are met:
(a) Each winding is equipped with individual overload protection sized
according to its full-load current.
(b) The branch-circuit conductors supplying each winding are sized
according to the full-load current of the
highest full-load current winding.
(c) The controller for each winding has a horsepower rating not less than
that required for the winding having the highest horsepower rating.
(5) Power Electronic
Devices. Suitable fuses shall be permitted in lieu of devices listed in
Table 430.52 for power electronic devices in a solid-state motor controller
system, provided that the marking for replacement fuses is provided adjacent
to the fuses.
(6) Self-Protected
Combination Controller. A listed selfprotected combination controller
shall be permitted in lieu of the devices specified in Table 430.52.
Adjustable instantaneous-trip settings shall not exceed 1300 percent of
full-load motor current for other than Design B energy-efficient motors and
not more than 1700 percent of full-load motor current for Design B
energy-efficient motors.
Informational Note: Proper application of self-protected combination
controllers on 3-phase systems, other than solidly grounded wye,
particularly on corner grounded delta
systems, considers the self-protected combination controllers’ individual
pole-interrupting capability.
(7) Motor Short-Circuit
Protector. A motor short-circuit protector shall be permitted in lieu
of devices listed in Table 430.52 if the motor short-circuit protector is
part of a listed combination motor controller having coordinated motor
overload protection and short-circuit and ground-fault protection in each
conductor and it will open the circuit at currents exceeding 1300 percent of
motor full-load current for other than Design B energy-efficient motors and
1700 percent of motor full-load motor current for Design B energy-efficient
motors.
Informational Note: A motor short-circuit protector, as used in this
section, is a fused device and is not an instantaneous trip circuit breaker.
(D) Torque Motors. Torque
motor branch circuits shall be protected at the motor nameplate current
rating in accordance with 240.4(B).
430.53 Several Motors or Loads on One Branch
Circuit.
Two or more motors or one or more motors
and other loads shall be permitted to be connected to the same branch
circuit under conditions specified in 430.53(D) and in 430.53(A), (B), or
(C). The branch-circuit protective device shall be fuses or inverse time
circuit breakers.m
(A) Not Over 1 Horsepower.
Several motors, each not exceeding 1 hp in rating, shall be permitted on
a nominal 120-volt branch circuit protected at not over 20 amperes or a
branch circuit of 600 volts, nominal, or less, protected at not over 15
amperes, if all of the following conditions are met:
(1) The full-load rating of each motor does not exceed 6 amperes.
(2) The rating of the branch-circuit short-circuit and groundfault
protective device marked on any of the controllers is
not exceeded.
(3) Individual overload protection conforms to 430.32
(B) If Smallest Rated Motor Protected.
If the branchcircuit short-circuit and ground-fault protective device is
selected not to exceed that allowed by 430.52 for the smallest rated motor,
two or more motors or one or more motors
and other load(s), with each motor having individual overload protection,
shall be permitted to be connected to a
branch circuit where it can be determined that the branchcircuit
short-circuit and ground-fault protective device will
not open under the most severe normal conditions of service that might be
encountered.
(C) Other Group Installations. Two or more motors of any rating or
one or more motors and other load(s), with each
motor having individual overload protection, shall be permitted to be
connected to one branch circuit where the motor
controller(s) and overload device(s) are
(1) installed as a listed factory assembly and the motor
branch-circuit short-circuit and ground-fault protective device either is
provided as part of the assembly or is specified by a marking on the
assembly, or
(2) the motor branch-circuit short-circuit and ground-fault protective
device, the motor controller(s), and overload device(s)
are field-installed as separate assemblies listed for such use and
provided with manufacturers’ instructions for use with
each other, and
(3) all of the following conditions are complied with:
(1) Each motor overload device is either (a) listed for group
installation with a specified maximum rating of fuse, inverse time circuit
breaker, or both, or (b) selected such
that the ampere rating of the motor-branch short-circuit and ground-fault
protective device does not exceed that
permitted by 430.52 for that individual motor overload device and
corresponding motor load.
(2) Each motor controller is either
( a) listed for group installation
with a specified maximum rating of fuse, circuit
breaker, or both, or
(b) selected such that the ampere rating of the motor-branch
short-circuit and ground-fault protective device does not exceed that
permitted by 430.52 for that individual controller and corresponding motor
load.
(3) Each circuit breaker is listed and is of the inverse time type.
(4) The branch circuit shall be protected by fuses or inverse time
circuit breakers having a rating not exceeding that specified in 430.52 for
the highest rated motor connected
to the branch circuit plus an amount equal to the sum of the full-load
current ratings of all other motors and the
ratings of other loads connected to the circuit. Where this calculation
results in a rating less than the ampacity of the
supply conductors, it shall be permitted to increase the maximum rating
of the fuses or circuit breaker to a value
not exceeding that permitted by 240.4(B).
(5) The branch-circuit fuses or inverse time circuit breakers are not
larger than allowed by 430.40 for the overload
relay protecting the smallest rated motor of the group.
(6) Over current protection for loads other than motor loads shall be in
accordance with Parts I through VII of Article 240.
Informational Note: See 110.10 for circuit impedance and other
characteristics.
(D) Single Motor Taps.
For group installations described above, the conductors of any tap supplying
a single motor
shall not be required to have an individual branch-circuit short-circuit
and ground-fault protective device, provided
they comply with one of the following:
(1) No conductor to the motor shall have an ampacity less than that of
the branch-circuit conductors.
(2) No conductor to the motor shall have an ampacity less than one-third
that of the branch-circuit conductors, with a minimum in accordance with
430.22, the conductors to the motor overload device being not more
than 7.5 m (25 ft) long and being protected from physical damage by being
enclosed in an approved raceway or by use of other approved means.
(3) Conductors from the branch-circuit short-circuit and ground-fault
protective device to a listed manual motor
controller additionally marked “Suitable for Tap Conductor Protection in
Group Installations,” or to a branchcircuit protective device, shall be
permitted to have an
ampacity not less than one-tenth the rating or setting of the
branch-circuit short-circuit and ground-fault protective device. The
conductors from the controller to the motor shall have an ampacity in
accordance with 430.22. The
conductors from the branch-circuit short-circuit and ground-fault
protective device to the controller shall
(1) be suitably protected from physical damage and enclosed either by
an enclosed controller or by a raceway and be
not more than 3 m (10 ft) long or
(2) have an ampacity not less than that of the branch-circuit
conductors.
430.54 Multimotor and Combination-Load Equipment.
The rating of the branch-circuit short-circuit and ground-fault
protective device for multimotor and combination-load equipment shall not
exceed the rating marked on the equipment in
accordance with 430.7(D).
430.55 Combined Overcurrent Protection.
Motor branch circuit short-circuit and
ground-fault protection and motor overload protection shall be permitted to
be combined in a
single protective device where the rating or setting of the device
provides the overload protection specified in 430.32.
430.56 Branch-Circuit Protective Devices — In Which
Conductor .
Branch-circuit protective devices shall
comply with the provisions of 240.15.
430.57 Size of Fuseholder.
Where fuses are used for motor
branch-circuit short-circuit and ground-fault protection, the fuseholders
shall not be of a smaller size than required to accommodate the fuses
specified by Table 430.52.
Exception: Where fuses having time delay
appropriate for the starting characteristics of the motor are used, it shall
be permitted to use fuseholders sized to fit the fuses that are used.
430.58 Rating of Circuit Breaker .
A circuit breaker for motor branch-circuit
short-circuit and ground-fault protection shall have a current rating in
accordance with 430.52
and 430.110.
V. Motor
Feeder Short-Circuit and Ground-Fault Protection
430.61 General.
Part V specifies protective devices
intended to protect feeder conductors supplying motors against overcurrents
due to short circuits or grounds.
Informational Note: See Informative Annex D, Example D8.
430.62 Rating or Setting — Motor Load.
(A) Specific
Load. A feeder supplying a specific fixed motor load(s) and
consisting of conductor sizes based on 430.24 shall be provided with a
protective device having a
rating or setting not greater than the largest rating or setting of the
branch-circuit short-circuit and ground-fault protective device for any
motor supplied by the feeder [based on
the maximum permitted value for the specific type of a protective device
in accordance with 430.52, or 440.22(A) for hermetic refrigerant
motor-compressors], plus the sum
of the full-load currents of the other motors of the group.
Where the same rating or setting of the branch-circuit short-circuit and
ground-fault protective device is used on
two or more of the branch circuits supplied by the feeder, one of the
protective devices shall be considered the largest
for the above calculations.
Exception No. 1: Where one or more instantaneous trip circuit breakers or
motor short-circuit protectors are used for motor branch-circuit
short-circuit and ground-fault protection as permitted in 430.52(C), the
procedure provided above for determining the maximum rating of the feeder
protective device shall apply with the following provision: For the purpose
of the calculation, each instantaneous trip circuit breaker or motor
short-circuit protector shall be assumed to have a rating not exceeding the
maximum percentage of motor full-load current permitted by Table 430.52 for
the type of feeder protective device employed.
Exception No. 2: Where the feeder overcurrent protective device also
provides overcurrent protection for a motor control center, the provisions
of 430.94 shall apply.
Informational Note: See Informative Annex D, Example D8.
(B) Other Installations.
Where feeder conductors have an ampacity greater than required by 430.24,
the rating or setting
of the feeder overcurrent protective device shall be permitted to be
based on the ampacity of the feeder conductors.
430.63 Rating or Setting
— Motor Load and Other Load(s).Where a
feeder supplies a motor load and other load(s), the feeder protective device
shall have a rating not less than that required for the sum of the other
load(s) plus the following:
(1) For a single motor, the rating permitted by 430.52
(2) For a single hermetic refrigerant motor-compressor, the rating
permitted by 440.22
(3) For two or more motors, the rating permitted by 430.62
Exception: Where the feeder overcurrent device provides the overcurrent
protection for a motor control center, the provisions of 430.94 shall apply.
VI. Motor Control Circuits
430.71 General.
Part VI contains modifications of the
general requirements and applies to the particular conditions of motor
control circuits.
Informational Note: See 430.9(B) for equipment device terminal
requirements
430.72 Overcurrent Protection.
(A) General.A motor
control circuit tapped from the load side of a motor branch-circuit
short-circuit and ground-fault
protective device(s) and functioning to control the motor(s) connected to
that branch circuit shall be protected against
overcurrent in accordance with 430.72. Such a tapped control circuit
shall not be considered to be a branch circuit
and shall be permitted to be protected by either a supplementary or
branch-circuit overcurrent protective device(s).
A motor control circuit other than such a tapped control circuit shall be
protected against overcurrent in accordance
with 725.43 or the notes to Table 11(A) and Table 11(B) in Chapter 9, as
applicable.
(B) Conductor
Protection. The overcurrent protection for conductors shall be provided
as specified in 430.72(B)(1)
or (B)(2).
Exception No. 1: Where the opening of the control circuit would create a
hazard as, for example, the control circuit of a fire pump motor, and the
like, conductors of control circuits shall require only short-circuit and
ground-fault protection
and shall be permitted to be protected by the motor branch circuit
short-circuit and ground-fault protective device(s).
Exception No. 2: Conductors supplied by the secondary side of a
single-phase transformer having only a two-wire (single-voltage) secondary
shall be permitted to be protected by overcurrent protection provided on the
primary (supply) side of the transformer, provided this protection does not
exceed the value determined by multiplying the appropriate maximum rating of
the overcurrent device for the secondary conductor from Table 430.72(B) by
the secondary-to-primary voltage ratio. Transformer secondary conductors
(other than two-wire) shall not be considered to be protected by the primary
overcurrent protection.
(1) Separate Overcurrent
Protection. Where the motor branch-circuit short-circuit and
ground-fault protective device
does not provide protection in accordance with 430.72(B)(2), separate
overcurrent protection shall be provided. The over
current protection shall not exceed the values specified in Column A of
Table 430.72(B).
(2) Branch-Circuit Overcurrent
Protective Device. Conductors shall be permitted to be protected by
the motor branch-circuit short-circuit and ground-fault protective device
and shall require only short-circuit and ground-fault protection. Where
the conductors do not extend beyond the motor
control equipment enclosure, the rating of the protective device(s) shall
not exceed the value specified in Column B of
Table 430.72(B). Where the conductors extend beyond the motor control
equipment enclosure, the rating of the protective
device(s) shall not exceed the value specified in Column C of Table
430.72(B).
(C) Control Circuit
Transformer. Where a motor control circuit transformer is provided, the
transformer shall be protected in accordance with 430.72(C)(1), (C)(2),
(C)(3),
(C)(4), or (C)(5).
Exception: Overcurrent protection shall be omitted where the opening of
the control circuit would create a hazard as, for example, the control
circuit of a fire pump motor and the like.
(1) Compliance with Article 725.
Where the transformer
supplies a Class 1 power-limited circuit, Class 2, or Class 3
remote-control circuit complying with the requirements of
Article 725, protection shall comply with Article 725.
(2) Compliance with Article 450.Protection
shall be permitted to be provided in accordance with 450.3.
(3) Less Than 50 Volt-Amperes.
Control circuit transformers rated less than 50 volt-amperes (VA) and that
are an integral part of the motor controller and located within the motor
controller enclosure shall be permitted to be protected by primary
overcurrent devices, impedance limiting means, or other
inherent protective means.
(4) Primary Less Than 2 Amperes.
Where the control
circuit transformer rated primary current is less than
2 amperes, an overcurrent device rated or set at not more
than 500 percent of the rated primary current shall be
permitted in the primary circuit.
(5) Other Means.
Protection shall be permitted to be provided by other approved means.
430.73 Protection of Conductors from Physical Damage.
Where damage to a motor control circuit would constitute a hazard, all
conductors of such a remote motor control circuit that are outside the
control device
itself shall be installed in a raceway or be otherwise protected from
physical damage.
430.74 Electrical Arrangement of Control Circuits.
Where one conductor of the motor control
circuit is grounded, the motor control circuit shall be arranged so that a
ground fault in the control circuit remote from the motor controller will
(1) not start the motor and
(2) not bypass manually operated shutdown devices or automatic safety
shutdown device
-----========-------
VIII. Motor Control Centers
430.92 General.Part
VIII covers motor control centers in stalled for the
control of motors, lighting, and power circuits.
430.94 Overcurrent Protection.
Motor control centers shall be provided with overcurrent
protection in accordance with Parts I, II, and VIII of Article 240. The
ampere rating or setting of the overcurrent protective device shall not
exceed the rating of the common power bus.
This protection shall be provided by
(1) an overcurrent protective device located ahead of the
motor control center or
(2) a main overcurrent protective device located within the motor control
center.
430.111 Switch or Circuit Breaker as Both Controller and
Disconnecting Means .
A switch or circuit breaker shall be permitted to be
used as both the controller and disconnecting means if it complies with
430.111(A) and is one of the
types specified in 430.111(B).
(A) General.
The switch or circuit breaker complies with the requirements for
controllers specified in 430.83, opens all ungrounded conductors to the
motor, and is protected by an
overcurrent device in each ungrounded conductor (which shall be permitted
to be the branch-circuit fuses).
The overcurrent device protecting the controller shall be permitted to be
part of the controller assembly or shall be permitted to be separate.
An autotransformer-type controller shall be provided with a separate
disconnecting means.
(B) Type.
The device shall be one of the types specified in 430.111(B)(1), (B)(2),
or (B)(3).
(1) Air-Break Switch. An air-break switch, operable directly by applying
the hand to a lever or handle.
(2) Inverse Time Circuit Breaker. An inverse time circuit breaker
operable directly by applying the hand to a lever or
handle. The circuit breaker shall be permitted to be both power and
manually operable.
(3) Oil Switch. An oil switch used on a circuit whose rating does not
exceed 600 volts or 100 amperes, or by special permission on a circuit
exceeding this capacity where under expert supervision. The oil switch shall
be permitted to be both power and manually operable.
430.112 Motors Served by Single Disconnecting Means.
Each motor shall be provided with an individual disconnecting means.
|